Viessmann Boiler: Check and replace burner refractory and cylinder burner

Updated · by Aurora Star Tech Inc.

Check and replace burner refractory and cylinder burner on a Viessmann boiler: Inspect the refractory ring and cylinder burner assembly.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HA 19, 28, 35

How to fix check and replace burner refractory and cylinder burner: step by step

  1. Remove the electrode block and ionization electrode B.
  2. Undo the three retaining clips C and remove the refractory ring D.
  3. Loosen the four Torx screws and remove the cylinder burner assembly E and assembly gasket F.
  4. Fit the new cylinder burner assembly and new gasket. Tighten to 31 lb.in. (3.5 Nm).
  5. Reinstall the refractory ring and clips.
  6. Reinstall the electrode block and ionization electrode. Tighten to 40 lb.in. (4.5 Nm).
  7. Check burner gasket A for damage. Generally replace it every 2 years.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Viessmann Vitodens 200-W B2HA service instructions, p. 21. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.