Viessmann Boiler: Check and replace burner refractory and cylinder burner
Check and replace burner refractory and cylinder burner on a Viessmann boiler: Inspect the refractory ring and cylinder burner assembly.
Applies to: Vitodens 200-W B2HA 19, 28, 35
How to fix check and replace burner refractory and cylinder burner: step by step
- Remove the electrode block and ionization electrode B.
- Undo the three retaining clips C and remove the refractory ring D.
- Loosen the four Torx screws and remove the cylinder burner assembly E and assembly gasket F.
- Fit the new cylinder burner assembly and new gasket. Tighten to 31 lb.in. (3.5 Nm).
- Reinstall the refractory ring and clips.
- Reinstall the electrode block and ionization electrode. Tighten to 40 lb.in. (4.5 Nm).
- Check burner gasket A for damage. Generally replace it every 2 years.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitodens 200-W B2HA service instructions, p. 21. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.