Viessmann Boiler: Check and clean ignition and ionisation electrodes
Check and clean ignition and ionisation electrodes on a Viessmann boiler: Check electrode wear, contamination and clearances.
Applies to: Vitodens 100-W, WB1B
Common causes of check and clean ignition and ionisation electrodes
- Worn, contaminated or warped electrodes
- Incorrect electrode clearance
How to fix check and clean ignition and ionisation electrodes: step by step
- Check the ignition and ionisation electrodes for wear, contamination or warping.
- Clean the electrodes with a small brush or emery paper.
- Check the clearances. If they are wrong or the electrodes are damaged, replace the electrode block and gasket and align the new parts.
- Tighten the electrode fastening screws to 3.5 Nm (31 lb.in.) with a calibrated torque wrench.
- Refit the grounding wire.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitodens 100-W, WB1B installation and service instructions, p. 69. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.