Viessmann Boiler: Boiler piped into a heating/cooling system with chiller
Boiler piped into a heating/cooling system with chiller on a Viessmann boiler: When the boiler is used with a chiller, the chilled water must be piped in parallel with the boiler using valves, so chilled water cannot enter the boiler. Heating coils in air handlers that see refrigerated air need flow control valves or equivalent to stop gravity circulation during cooling. Follow the chiller maker's installation requirements as well.
Applies to: Vitodens 200-W B2HB boiler connected to a water chiller (heating/cooling application)
Common causes of boiler piped into a heating/cooling system with chiller
- Chilled medium entering the boiler
- Gravity circulation through the boiler during the cooling cycle
How to fix boiler piped into a heating/cooling system with chiller: step by step
- Pipe the chilled medium in parallel with the boiler.
- Fit valves so chilled medium cannot enter the boiler.
- Fit flow control valves on heating coils in air handlers that may see refrigerated air.
- Label the changeover valves v1 and v2.
- Run the circulating pump from its own on/off switch, not from the boiler pump aquastat.
- When cooling season starts, close v1 and open v2.
- When heating season starts, close v2 and open v1.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Installation Instructions, p. 43. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.