Settings shortcuts: Boiler tips (part 4 of 10)
Short, practical technician tips on settings shortcuts for boiler. Check each one against the manual for your exact model before acting.
Change the operating program for a heating circuit
Viessmann · Vitocrossal 300 CA3B Series 2.5 to 6.0
The operating program is set at the system and lead boiler section 1 only. Choose Heating and DHW, DHW only, or Standby mode for each heating circuit.
- From the home screen, select Heating circuit 1, 2 or 3.
- Open the operating program selection.
- Select the required operating program.
- Confirm the setting.
Change the reduced (night) room temperature
Viessmann · Vitotronic 300 Model GW2
Sets the room temperature used during the reduced periods. Factory setting is freeze-up protection at 3°C / 37°F, active from 22:00 to 06:00. Adjustable from 4 to 37°C (39 to 99°F). Setting 3°C shows 'Freeze-up protection' in the display.
- Open the hinged cover on the programming unit.
- Press the heating circuit selector button so it lights up.
- Press the reduced-temperature button; the current setting flashes.
- Press the up or down button until the required value appears.
- Press OK to confirm; the value stops flashing and is stored.
- Close the hinged cover.
Change the reduced room temperature
Viessmann · Vitotrol 300 remote control
Reduced room temperature is adjustable from 37 to 99 °F (3 to 37 °C). Default is frost protection at 37 °F / 3 °C from 22:00 to 06:00.
- Open the flip-down cover of the remote control.
- Press the reduced room temperature key.
- Use the up/down keys to choose the temperature.
- Press to confirm; the value is saved.
- Close the cover.
Change the room temperature set-point
Viessmann · Vitodens 200-W B2HA 112–530
Example: change the set-point from 68 °F to 79 °F (20 °C to 26 °C).
- Select 'Heating'.
- Select the heating circuit.
- Press OK.
- Select room temperature set-point and press OK.
- Change the value with the selector.
- Press OK to accept, then exit.
Change the room temperature setback
Viessmann · Vitodens 200-W B2HB heating circuits
Sets the reduced room temperature setpoint. Example: 41°F to 57°F (5°C to 14°C).
- Select Heating.
- Select the heating circuit.
- Press OK.
- Select Red. room temperature setpoint, then press OK.
- Change the value with the arrow keys.
- Accept with OK.
- Exit the menu.
Change the room temperature setpoint or setback for a heating circuit
Viessmann · Vitodens 200-W B2HA 45, 60
Use the control unit's heating menu to set the day setpoint or the setback (reduced) temperature for each heating circuit. Some steps in the source sequence are missing button symbols, so follow the menu labels.
- Select Heating from the menu.
- Choose the heating circuit.
- Press OK, then select the room temperature setpoint (or reduced setpoint for setback).
- Press OK, change the value with the arrow keys, then accept with OK.
- Exit the menu.
Change the room temperature with the rotary knob
Viessmann · Versatronik COMO OT
In normal mode the system follows the set room temperature (default 20°C/68°F). The knob moves it up to ±5°C/9°F, about 1°C/2°F per dot. The night (economy) temperature is not changed.
- Turn the rotary knob clockwise to make the room warmer.
- Turn it counterclockwise to make the room colder.
- Check that the night (economy) temperature is unchanged after adjusting.
Change the standard room temperature setpoint
Viessmann · Vitodens 200-W B2HB heating circuits
Sets the room temperature setpoint from the standard menu. Example: 68°F to 79°F (20°C to 26°C).
- Select Heating.
- Select the heating circuit.
- Press OK.
- Select Room temperature setpoint, then press OK.
- Change the value with the arrow keys.
- Accept with OK.
- Exit the menu.
Changing heating curve slope and shift
Viessmann · Each heating circuit, single boiler and cascade
Adjusts slope or shift for one heating circuit. Changing the shift moves the curve up or down in parallel.
- Tap Menu.
- Tap Heating circuit 1, 2 or 3.
- Tap Heating.
- Tap Heating curve.
- Use +/- to set the required slope or shift.
- Tap OK to confirm.
Changing slope or shift of the heating curve
Viessmann · Vitocontrol-S, VD2/CT3/CM2 heating circuits
Slope changes the steepness of the heating curve. Shift moves the curve up or down. Use the change table as a guide and change one value at a time.
- Open the hinged cover on the programming unit.
- Press the heating circuit selector button; the button lights up.
- Press the button for Slope or the button for Shift.
- Press the button(s) until the required value is displayed.
- Press the confirm button; the display shows the boiler temperature.
- Close the hinged cover.
Changing the set room temperature with the dial
Viessmann · Versatronik COMO OT in Normal mode
In Normal mode the set room temperature defaults to 20°C (68°F). The dial changes it by up to ±5°C (±9°F). Each dot is about 1°C (2°F). The night (economy) temperature is not changed.
- In Normal mode, turn the dial clockwise to warm the room.
- Turn the dial counterclockwise to cool the room.
- Read the new set point in the display.
Changing the space heating time program
Viessmann · HK1S and HK3S
Space heating time phases are set per day or for all days together. Up to 4 phases per day.
- Open the hinged cover on the programming unit.
- Press the heating time program button; the display shows the heating program.
- Press up or down to choose '1-7' (all days) or a single weekday.
- Confirm; set the ON and OFF times for heating phase 1 and confirm each.
- Set phases 2 to 4 the same way, then close the cover.
- After the last confirmation the basic display returns.
Changing the standard display
Viessmann · Vitotrol 300A remote control
Show heating circuit 2 or 3 details in the header of the standard display.
- Open the extended menu.
- Select Settings, then Standard display.
- Select the heating circuit.
Choose automatic or individual DHW time program
Viessmann · Vitotronic 300 Model GW2
Automatic mode runs domestic hot water in parallel with the heating program, starting 30 minutes earlier. The DHW re-circulation pump follows the DHW time program. Individual mode lets you set your own times.
- Open the hinged cover on the programming unit.
- Press the heating circuit selector button so it lights up.
- Press the DHW time program button; 'DHW time program' appears.
- Use up or down to select 'Automatic?' or 'Individual?'.
- Press OK to confirm.
Coding address groups for temperature and cascade control
Viessmann · Vitocontrol-S VD2/CT3/CM2 cascade
These coding address groups affect boiler temperature control and cascade control. Full descriptions are in the coding overview.
- Boiler temperature control: coding 02 to 06, 08 to 0b and 13 to 1C.
- Cascade control: coding 35 to 3F and 41 to 4A.
- Boiler sequence is set with coding 2 and the boiler sequence selection.
Coding addresses for remote control functions
Viessmann · Vitotrol 200 and Vitotrol 300
Function changes for Vitotrol 200 and Vitotrol 300 are made through coding addresses A0, b0 to b9, C0 to C2, E1 and E2. E1 sets the room temperature setting range.
- Refer to the coding overview in the manual.
- Change the required coding address on the control unit.
Coding addresses referenced in these pages
Viessmann · Vitotronic 100 GC1 and Vitocontrol-S VD2/CT3/CM2
Coding address 06 holds the high limit setting that was changed. Coding address 40 sets the valve actuator operating time.
- After changing the high limit cams, check coding address 06.
- Set valve operating time (5 to 199 sec) at coding address 40.
Coding groups
Viessmann · Vitocrossal 300 CA3B Series 2.5 to 6.0
Coding is split into groups: General, Burner control unit, DHW, Solar, Heating circuit 1/2/3, Boiler, Cascade, and All coding. All coding lists every item in ascending order, except the Solar group. Heating circuit names change if the circuits were named individually.
- Select the group you need.
- Select the required value from the tables in the coding section.
- Tap the accept button to save.
Codings changeable in coding level 1
Viessmann · Vitotronic 200 KW2, coding level 1
Only these addresses can be changed in coding level 1. The list may vary with the installed equipment.
- Change system type.
- Change burner type.
- Set maximum boiler water temperature.
- Set DHW priority (boiler circuit).
- Set summer energy saving mode (boiler circuit).
- Set DHW priority (mixing valve circuit).
- Set summer energy saving mode (mixing valve circuit).
- Set supply low limit (mixing valve circuit).
- Set supply high limit (mixing valve circuit).
Comfort mode on a heating circuit
Viessmann · Heating circuits on Vitotronic 300-K
Comfort mode heats the rooms to the set comfort room temperature, and DHW is heated first if the contractor has not changed the settings.
- From the home screen, select the heating circuit in the header.
- Select comfort mode and set it to ON.
- Set the required room temperature for comfort mode and confirm.
- To end it, set comfort mode to OFF and confirm.
Comfort mode ON/OFF
Viessmann · Vitocrossal 300 CA3B Series 2.5 to 6.0
Comfort mode heats the rooms to a set target temperature. When enabled, DHW is heated to its set temperature first, before central heating starts. The DHW recirculation pump runs if installed.
- From the home screen, select the heating circuit.
- Select Comfort mode.
- Set ON to enable it, then set the required room temperature target and confirm, or set OFF to disable it.
- Confirm the setting.
Comfort mode: start and end
Viessmann · Central heating for each heating circuit
Comfort mode heats rooms to a set comfort temperature. DHW is heated first if the contractor has not changed the settings, and the DHW recirculation pump runs if installed. It ends automatically after 8 hours or when the time program switches to standard heating.
- Start: Menu, Heating, Heating circuit 1/2/3, Comfort mode, select the white frame, tap OK, set the comfort room temperature, tap OK.
- End: Menu, Heating, Heating circuit 1/2/3, Comfort mode, the white frame resets, tap OK.
- Repeat for each heating circuit connected to the Vitotronic 300-K.
- To stop central heating instead, set the operating program to DHW only or Standby mode and tap OK.
Copy, change or delete time phases
Viessmann · Time program heating, Heating circuit 1
A time program for one day can be copied to other days. Individual time phases can also be edited or removed.
- To copy: Menu, Heating, Heating circuit 1, Time program heating, select the source day, tap Copy, select the target days, then press OK.
- To change a start point: Menu, Heating, Heating circuit 1, Time program heating, select the day, tap Edit, select the time phase, adjust the start point, then tap OK.
- To delete a time phase: Menu, Heating, Heating circuit 1, Time program heating, select the day, tap Edit, select the time phase, tap x, then tap OK.
Deleting a time phase
Viessmann · Central heating and DHW time programs
Two ways to remove a time phase in the time program.
- Set the end time of the phase to the same time as its start point.
- Or set the start point to a time before 00:00 h. The display then shows the phase as - - : - -.
Designate heating circuit names
Viessmann · Vitodens 200-W B2HA 45, 60
Heating circuits default to Heating circuit 1, 2 and 3 (if installed). Names can be changed to suit the system. The text refers to the Operating Instructions for the entry steps.
- Refer to the Operating Instructions for entering heating circuit names.
DHW default display controls
Viessmann · Vitocrossal 200 CI2 DHW display, not for Aquastat tank systems
The DHW default display lets you adjust the DHW temperature, turn DHW heating on or off, open the DHW time program and start or stop one-off DHW heating. This display is not available on systems with a storage tank that uses a temperature switch (such as an Aquastat).
- Use the up or down buttons to change the DHW temperature.
- Use the on/off button to turn DHW heating ON or OFF.
- Use the time program button to open the DHW time program.
- Use the one-off DHW heating button to start or stop a one-off heat-up outside the time program.
DHW heating once outside the time program
Viessmann · Vitocrossal 300 CA3B
This starts one DHW heating cycle outside the time program. It avoids unintended central heating at standard room temperature.
- Make sure the operating program Heating and DHW or DHW only is set for at least one heating circuit.
- Enable Comfort mode.
- Disable Comfort mode straight away.
DHW recirculation pump depends on coding address 53
Viessmann · Vitodens 200-W B2HA 45, 60 DHW recirculation
The function of the DHW recirculation pump in the layouts is set by the coding of address 53. The diagrams flag this with a footnote on each layout.
- Set coding address 53 to match the DHW recirculation pump function required by the layout.
DHW recirculation pump function depends on coding address 53
Viessmann · Vitodens 200-W B2HB layouts with 28/20 pumps
In the layouts, the DHW recirculation pump 28/20 and the heating circuit pump 28/20 are marked as working according to coding address 53.
- Check coding address 53 before setting up a DHW recirculation or 28/20 heating circuit pump.
DHW recirculation pump schedule
Viessmann · Systems with DHW recirculation pump
Automatic mode runs the DHW recirculation pump alongside the DHW heating program. Enabling it is only advisable when DHW is actually drawn, to avoid wasted energy.
- Open the extended menu and select DHW.
- Select DHW recirc pump schedule.
- Choose Automatic, or Individual to set up to four phases per day.
- Set start and end times for each phase.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.