Retrieve fault history (fault memory)

Viessmann · Vitotronic 200 KW2 fault memory

All past faults are stored and can be scanned from the most recent one backwards. Button names are not legible in the extracted text, so confirm the buttons on the unit or the programming unit.

  1. Press the two buttons shown together for about 2 seconds to enter error history scan mode.
  2. Read the first entry, which shows the most recent fault.
  3. Use the up or down button to step through the stored codes, up to 10 entries back.
  4. Press the exit button to leave error history scan mode.
  5. To delete all stored fault codes, press the button shown in the manual while in scan mode.

Retrieving the fault memory (error history)

Viessmann · Vitotronic 100 GC1 programming unit

Stored faults are kept and can be scanned, starting with the most recent. Up to 10 stored codes can be reviewed and the whole list can be cleared.

  1. Press the two buttons together for about 2 seconds to start error history scanning.
  2. Scroll through the stored codes with the up or down button. Code 1 is the most recent.
  3. Press the exit button to leave scanning.
  4. To delete all stored codes, use the delete function while in scanning mode.

Run a brief scan

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

Brief scan shows temperatures, software versions and connected components on 9 lines with 6 fields each.

  1. Press OK together with the second control button for about 4 seconds.
  2. Select Diagnosis.
  3. Select Brief scan.
  4. Press OK to view the 9 lines of data.

Run a relay test

Viessmann · Vitotronic 100 KW10B

Forces individual relays on to check outputs. It overrides all other control functions.

  1. Set dial switch S2 to the relay test position needed (see the dial switch table).
  2. Check the output responds as expected.
  3. Return S2 to position 0 for normal operation.

Run LON participant check

Viessmann · LON fault manager control

Tests communication with the devices connected to the fault manager. Results show as OK or Not OK per participant.

  1. Confirm the control is fault manager (code 79:1) and the participant list is up to date.
  2. Press OK and the second key (symbol not legible in the text) together for about 4 seconds.
  3. Select 'Service functions'.
  4. Select 'Participant check'.
  5. Select the participant (for example participant 10).
  6. Read the result: OK means passed, Not OK means failed.

Run the actuator test

Viessmann · Vitocrossal 200 CI2 service menu

Forces outputs to check actuators. When the test starts, all actuators are disabled and valves move to their central position. Functions stay active for 30 seconds. If a function cannot run because of the current process, it is interrupted and a prompt appears. If max heating output is restricted by parameter 596.0, the boiler is skipped in the test.

  1. Enter the service menu and select Actuator test.
  2. Confirm the security prompt.
  3. Select the required group.
  4. Tap the required actuator function. Several can run at once.
  5. Confirm if prompted. Functions run for 30 seconds.
  6. End the actuator test with the exit option.

Run the operating conditions scan

Viessmann · Vitotronic 200-H, Model HK1M

Reads live operating values such as outdoor, return, supply and room temperatures, plus clock data.

  1. Press the scan button (symbol not legible in source).
  2. Select the operating condition with the arrow buttons.
  3. Press OK to view it.
  4. To leave, press the button shown in the source (symbol not legible).

Run the relay test

Viessmann · Vitotronic 200-H

The relay test switches individual outputs on and off so you can confirm the wiring and the mixing valve actuator.

  1. Press the 9 button and the second button (symbol not legible in the source) together for about 2 seconds to start the relay test.
  2. Use the up or down arrow to select the relay output.
  3. Press OK to finish the relay test.

Run the temperatures and quick scan

Viessmann · Vitotronic 200-H, Model HK1M

Use this to read live temperatures and software or device data from the control unit.

  1. Press 9 and r together for about 2 seconds.
  2. Select the scan you need with the arrow buttons.
  3. Press OK to view it.

Safety temperature limiter (FHL) test

Viessmann · Heat generator with safety temperature limiter

The FHL test checks the safety temperature limiter of the heat generator.

  1. Start the FHL test with the F button.
  2. Use the shaft encoder to find the boiler and select it with the F button.
  3. Read the heat generator temperature on the display.
  4. Press and hold the Start button until the STL activates; the burner runs, all pumps stop and all mixing valves close.
  5. Watch the temperature on the display during the test.

Scan central heating time phases at a glance

Viessmann · Central heating time program

Shows all preset central heating phases on a time slot graphic (0 to 24 h scale).

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button until it lights up.
  3. Press the two time program buttons together; the preset phases appear on the time slot graphic.
  4. Close the hinged cover.

Scan current information (300-K)

Viessmann · Vitotronic 300-K

The extended menu groups information as General, Heating circuit 1, 2 and 3, DHW, Solar and Reset data. Named heating circuits show their custom name.

  1. Open the extended menu.
  2. Select "Information".
  3. Select the group.
  4. Select the required scan.

Scan current system information

Viessmann · Control

Groups available in the main menu: General, Burner, Heating circuit 1, 2 and 3, DHW, Solar energy, Reset data and Service address. Available groups depend on the connected components and settings. Detailed scan options are in the Scanning options chapter (p. 32).

  1. Press Menu, then Information.
  2. Select the required information group.

Scan groups on Vitotronic 300-K

Viessmann · Vitotronic 300-K MW1B

Scan values are split into groups. If heating circuits have names, the name is shown instead of HC1 to HC3.

  1. Open the extended menu.
  2. Select Information.
  3. Select the group: General, Heating circuit 1, Heating circuit 2, Heating circuit 3, DHW, Solar or Reset data.
  4. Select the required scan value.

Scan heating time cycles on a time line

Viessmann · Vitotronic 300 Model GW2

Shows the preset heating cycles as a time line graphic without changing them.

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button so it lights up.
  3. Press the heating time program button and the 'Central Htg.' button together; the time line appears.
  4. Close the hinged cover.

Scan operating conditions (Vitotronic 100)

Viessmann · Vitotronic 100, GC1

Scans live readings from the Vitotronic 100 display. Which values show depends on the system layout. Scan readings include boiler temperature, sensor 17A and 17B temperatures, flue gas temperature, burner run hours for stage 1 and 2, and burner starts. The run hours and burner starts can be reset to 0.

  1. Press the scan button.
  2. Select the required scan with the up or down button.
  3. Press OK to view the value.
  4. Read the value. Flue gas and sensor 17A/17B readings only show when that sensor is fitted.
  5. To reset run hours or burner starts, use the reset button shown on the scan screen.

Scan operating conditions (Vitotronic 300-K)

Viessmann · Vitotronic 300-K, MW1S

Scans status readings such as participant number, holiday program status, outdoor, boiler, sensor, DHW, supply and return temperatures, room temperature, time and date, output states, pump states, mixing valve state and language. Items shown depend on equipment level.

  1. Press the scan button.
  2. Select the required scan with the up or down button.
  3. Press OK to view the value.
  4. Check pump ON/OFF states, output states and mixing valve open/closed.
  5. Check the displayed position in percent for valve or output positions where shown.

Scan operating data

Viessmann · Vitotronic 200 and 300-K

Operating data can be read in six areas. Data for mixing valve circuits and solar only shows if those components are installed. A "- - -" reading means a sensor that was scanned is faulty.

  1. Enter the service level.
  2. Select "Diagnosis".
  3. Select the required group, for example General.
  4. Check the readings. Treat "- - -" as a faulty sensor.

Scan operating data by area

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

Operating data is grouped in six areas under Diagnosis. Data for heating circuits with mixing valves and solar only shows when those components are installed. A sensor that is faulty shows - - - on the display.

  1. Enter the service level.
  2. Select Diagnosis.
  3. Select the required group, for example General, and read the values.

Scan operating data by group

Viessmann · Vitocrossal 300 CA3B Series 2.5 to 6.0

Operating data is grouped (General, Cascade, DHW, Heating circuit, Solar energy). A sensor reading of - - - means that the scanned sensor is faulty.

  1. From the home screen tap Service and enter the viservice password.
  2. Select Diagnosis.
  3. Select the group, for example General, and read the values.
  4. If a value shows - - -, check that sensor and its wiring.

Scan operating status information

Viessmann · Vitotronic 200 KW2

Shows the operating status data for the selected heating circuit. Items depend on the system equipment and coding. Includes holiday program dates, outdoor, supply, boiler, DHW, flue gas, return and room temperatures, burner operating hours, number of burner starts, fuel consumption, time, date, and pump and mixing valve status. Burner hours, starts and fuel consumption can be reset after maintenance.

  1. Select the heating circuit with its selector button.
  2. Press the operating status button once to enter the scan mode.
  3. Scroll through the data with the up/down button.
  4. After maintenance, reset burner operating hours, number of burner starts and fuel consumption to zero with the button shown in the manual.
  5. Press the button shown in the manual to exit the scan mode.
  6. Press the language button to set the permanent display language if needed.

Scan temperatures and boiler coding cards (diagnosis level)

Viessmann · Vitotronic 200 KW2

Diagnosis level shows live values for the selected heating circuit. Items only appear if the matching sensor or remote is connected. Scan items: damped and current outdoor temperature, desired and current supply, boiler, DHW, return water and room temperatures, max and current flue gas temperature, boiler coding card, and scans 1 to 4.

  1. Select the heating circuit with its selector button.
  2. Press the two buttons together for about 2 seconds to enter the diagnosis level.
  3. Scroll through the values with the up/down button.
  4. Press the reset button shown in the manual to set damped outdoor temperature or max flue gas temperature to the current value.
  5. Press the button shown in the manual to exit the diagnosis level.

Scan temperatures and operating data

Viessmann · Single-boiler and multi-boiler systems

Lets you read actual temperatures and run data. Only the values for connected sensors are displayed.

  1. Press the scan button. The first value appears on the display.
  2. Press the up/down button to step through the other values (see scanning table).
  3. Press the scan button again to exit. The display returns to the boiler temperature.

Scanning operating data (Diagnosis)

Viessmann · Vitodens 200-W B2HA 112/150/399/530

Operating data can be scanned in six groups. Mixing valve and solar data only show if those components are installed. A dashed display '- - -' means a scanned sensor is faulty.

  1. Press OK and the second key together for about 4 seconds.
  2. Select 'Diagnosis'.
  3. Select the required group, e.g. 'General', and press OK and the second key together for about 4 seconds.

Scanning operating data by group

Viessmann · Vitodens 200-W B2HA 80 to 100, 285 to 352

Operating data is grouped into six areas. Groups for mixing-valve heating circuits and solar only show values if those components are installed.

  1. Enter the service level.
  2. Select "Diagnosis".
  3. Select the required group, for example "General".

Scanning operating status values

Viessmann · Vitotronic 100 GC1 programming unit

Operating status values can be scanned in turn, showing temperatures, burner hours and starts. Some values only appear when the matching sensor or module is connected.

  1. Press the info button.
  2. Select the required status item with the up or down button.
  3. Press the scan button to start operating status scanning.
  4. Exit scanning when finished.

Scanning system data on Vitocontrol-S

Viessmann · Vitocontrol-S, VD2/CT3/CM2

Scan system values: participant number, holiday program with departure and return dates, outdoor temperature, boiler sequence, common supply temperature, boiler temperatures for boilers 1-4, flue gas temperature, sensors aJA and aJB, domestic hot water temperatures, supply temperature, room temperatures per heating circuit, time, date, outputs 20, 29 and 52, pump and mixing valve states, solar pump status and run hours, and LON equipment number. Only items with connected sensors or enabled functions appear.

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button; the button lights up.
  3. Press the scan button; the Participant No. appears.
  4. Press the button(s) to scan the other data.
  5. Press the exit button to leave scanning mode; the display returns to the boiler temperature.
  6. Close the hinged cover.
  7. To scan the active heating program, party or energy saving mode, press the heating circuit selector button; the active program button lights up.

Scanning temperatures and burner data on Vitotronic 100 GC1

Viessmann · Vitotronic 100, GC1 boiler controls

Scan actual temperatures and run data. Available items depend on the connected components. Burner hours and burner starts can be reset to 0.

  1. Open the hinged cover.
  2. Press the scan button; the first temperature appears.
  3. Press the button(s) to scan the other data.
  4. To reset burner hours or burner starts, press the button marked D while the value is shown.
  5. Press the exit button to leave scanning mode; the display returns to the boiler water temperature.

Scanning temperatures and operating status

Viessmann · Vitotronic 300 GW2 scan mode

Read actual temperatures and operating status without changing any settings. Some items only appear when the related sensor, pump, output or function is installed or enabled. The manual's conditions for each item are printed out of order, so check the wiring and settings if an item is missing. Items include outdoor, boiler, flue gas, sensor 17A and 17B, DHW temperatures, supply and room temperature, burner hours and starts, fuel consumption, time and date, burner and pump states, mixing valve position and language.

  1. Open the hinged cover on the programming unit.
  2. Press the heating circuit selector button; the button lights up.
  3. Press the scan button; the outdoor temperature appears first.
  4. Press the up or down arrow to scroll through the other values.
  5. Press the back or exit button to leave scan mode; the display returns to the boiler temperature.
  6. Close the hinged cover on the programming unit.

Scanning the fault display

Viessmann · Vitotronic 200-H fault display

Faults show as a flashing fault symbol U. Scanning reveals the fault number so the contractor can prepare before the call.

  1. Press the troubleshooting key to scan the fault.
  2. Read the fault number (example: 1, 1, 8).
  3. Press acknowledgement to clear the message from the display.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.