Reset & cancel: Boiler tips (part 6 of 8)
Short, practical technician tips on reset & cancel for boiler. Check each one against the manual for your exact model before acting.
Reset saved operating data
Viessmann · Vitotronic 200 and 300-K
Saved operating data such as hours run can be set back to 0. The adjusted outdoor temperature is reset to the actual outdoor temperature.
- Enter the service level.
- Select "Diagnosis", then "Reset data".
- Select the value to reset (for example "Burner starts") or "All details".
Reset saved operating data (Vitotronic 300-K)
Viessmann · Vitotronic 300-K
Saved operating data such as hours run can be reset to 0. The adjusted outside temperature value resets to the actual value.
- Press OK and the second button together for about 4 seconds.
- Select Diagnosis.
- Select Reset data.
- Select the required value, for example Solar circuit pump, or All details.
Reset scan data (burner hours, fuel use, solar data)
Viessmann · Vitocrossal 300 CA3B
Operator-level reset of stored counters from the Information menu. Solar items only apply with a solar thermal system.
- From the home screen, open Information.
- Choose Reset data.
- Select the data point to clear, or All data.
- Confirm, then tap Confirm again.
- Check that the footer shows the confirmation.
Reset service counter after maintenance
Viessmann · Vitocrossal 300 CA3B
Resets the hours-run and interval counters after service has been done. If not reset, the Service message comes back on the following Monday.
- From the home screen, open Service and enter the 'viservice' password.
- Open Service functions.
- Select Reset service. This sets the hours-run and interval counters to 0 and sets coding 24 in the Boiler group to 24:0.
Reset service display after service
Viessmann · Vitodens 222-F B2TB
Resets the hours-run and time interval counters so the service display restarts at 0.
- Press OK together with the second service key (symbol not legible on the page) for about 4 seconds.
- Select Service functions.
- Select Service reset.
Reset service interval after maintenance
Viessmann · Maintenance service reminder
After maintenance, the service counter for hours run and interval restarts. Coding 24 in the Boiler group returns to 24:0. If service was done early, set coding 24:1 to 24:0 so the interval restarts; otherwise Service appears again the following Monday.
- From the home screen tap Menu, then Service.
- Enter the viservice password.
- Tap Service functions, then Reset service.
- If the service was carried out early, set coding 24:1 in the Boiler group to 24:0.
Reset service interval after service
Viessmann · Vitotronic 200-H, Vitodens 200-W B2HB
Clears the hours run and time interval counters after the burner is serviced.
- Press OK and the second menu button together for about 4 seconds (symbol not legible in this copy).
- Select Service functions.
- Select Service reset.
- Hours run and time interval restart at 0.
Reset service maintenance counters
Viessmann · Vitocrossal 200 CI2 boilers
Clears maintenance messages. The selected hours-run and time-interval counters restart at 0. On multi-boiler systems this is done with the software tool.
- Open the service menu and enter password "viservice".
- Go to "System configuration", then "Boiler".
- Select parameter 1411.0 "Clear maintenance messages" and set it to "ON".
Reset solar energy and hours run data
Viessmann · Vitotronic 300-K with solar thermal system
With a solar system, the solar energy yield and the hours run for the solar circuit pump and output 22 can be reset to 0, or all of the above data can be reset together.
- Open the extended menu.
- Select "Information", then "Reset data".
Reset solar yield and pump run-hour data to 0
Viessmann · Vitotronic 300-K with solar thermal system
Resets the solar energy yield and run hours for the solar circuit pump and output 22. Can also reset all of these data at once.
- Open the extended menu.
- Select "Information".
- Select "Reset data".
- Choose the data to reset.
Reset stored burner hours, fuel consumption or other data
Viessmann · Vitocrossal 300 CA3B, all boiler sections
Burner hours run, fuel consumption, solar yield and solar pump hours can be cleared from the display. Data can be reset one at a time or all at once.
- From the home screen tap Menu.
- Tap Information.
- Tap Reset data.
- Select the data point required, or All details.
- Tap OK to confirm.
- Tap Confirm. The footer then shows the reset confirmation.
Reset the burner after an air-in-gas-line fault at start-up
Viessmann · Vitodens 200-W B2HA 19, 28, 35
Air in the gas supply pipe, especially with LPG, can cause a fault on first start-up.
- Wait about 5 seconds after the fault appears.
- Press the "R" button to reset the burner.
- The ignition procedure repeats automatically.
Reset the burner control unit after a fault
Viessmann · Vitocrossal 200 CM2 burner control unit
Fix the fault first, following the fault code measures in the listed order. Then reset the control with the reset button.
- Correct the fault using the measures for the displayed code, in the order given.
- Press and hold reset button R for longer than 0.5 seconds.
- Confirm the operating display returns.
Reset the burner hours run counter
Viessmann · Burner hours run counter
The burner hours run counter can be set back to zero from the scan display.
- Scan to the burner hours run item while the display is on.
- Press the D button to reset the burner hours run to 0.
Reset the burner service display after maintenance
Viessmann · Vitotronic 100 GC1, codings 21, 23 and 24
Coding 24 makes the service display appear. It does not clear itself after maintenance and must be reset by hand.
- Complete the burner maintenance.
- Reset the service display manually on the control unit.
- Confirm coding 21 or 23 if a new service interval is needed.
Reset the fixed high limit
Viessmann · Fixed high limit 7820 036
After the fixed high limit has cut out, it resets only once the water has cooled.
- Wait until the boiler water temperature has fallen about 15 K below the shut-down temperature.
- Press reset button E on the front of the programming unit.
Reset the fixed high limit (FHL)
Viessmann · Vitotronic 100 KW10B
The FHL is a manual reset limit. A click when it is pressed in shows it had tripped.
- Find the FHL reset pin, labelled with an E, on the control.
- Push the pin in with a ballpoint pen.
- If a click is heard, the limit had tripped and is now reset.
Reset the fixed high limit after a cut-out
Viessmann · Fixed high limit 7820 036
The fixed high limit locks out. It can only be reset after the water has cooled.
- Let the boiler water temperature fall about 15 K below the shut-down temperature.
- Press reset button E on the front of the programming unit.
Reset the hours run meter
Viessmann · Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0
The resettable hours run meter is cleared through menu item 2 and the status submenu.
- Hold button S for more than 2 seconds. The indicator blinks.
- Press Y until 2 shows under Service.
- Press S. 1 shows under Status.
- Press Y until 6 shows under Status.
- Press S to confirm. 1 under Service means the meter was deleted, 0 means it failed.
- Press S to return to the operating display.
Reset the manual reset limit switches
Viessmann · Supply water temperature limit switch (B) and flue gas temperature limit switch (C)
The supply water and flue gas temperature limit switches lock out mechanically once tripped. They are factory set and must not be adjusted. A switch can only be reset after the probe has cooled about 8 °C (14 °F) below its limit.
- Let the probe cool to about 8 °C (14 °F) below the limit temperature.
- Unscrew the reset cap and set it aside.
- Press to reset the switch.
- Reinstall the reset cap.
- If the switch will not reset, replace the switch.
Reset the Service display
Viessmann · Vitotronic 300 GW2
Clears the Service message after maintenance. If coding 24 is not reset, the message comes back at 07:00 on Monday.
- If service is done before the Service message shows, set coding 24: 1, then set 24: 0.
- Press the scan button to start the service scan.
- Scroll through service messages and confirm Acknowledge: Yes with OK.
- Press the exit button to end the service scan.
- After maintenance, set coding 24 from 1 back to 0.
- Reset burner hours, starts and fuel use from the operating status scan if needed.
Reset the service display after service
Viessmann · Vitodens 200-W B2HA, service interval
When coding 24:1 is set, the Service display appears at the service interval. The address is set automatically and must be reset by hand after service is done.
- Complete the burner service.
- Reset the Service display manually in the service menu.
- Confirm the service interval (21 or 23) is set as required.
Reset the service interval
Viessmann · Vitotronic 300 GW6B boiler control unit
Resetting restarts the hours-run and interval counters at 0 and sets coding 24 in the Boiler group to 24:0.
- From the home screen, tap Menu, then Service.
- Enter the viservice password.
- Tap Service functions, then Reset service.
Reset the service interval after maintenance
Viessmann · Vitocrossal 300 CA3B Series 2.5 to 6.0
Resetting the service interval sets hours run and the interval back to 0 and coding 24 in the Boiler group to 24:0. If service is done early, set coding 24:1 back to 24:0; otherwise Service will show again the following Monday. Service limits are set in codings 21 and 23 in the Boiler group.
- From the home screen tap Service and enter the viservice password.
- Select Service functions, then Reset service.
- If maintenance was done early, set coding 24:1 in the Boiler group to 24:0.
Resetting a burner fault shutdown
Viessmann · Vitocrossal 200 CI2 burner control
Gas pressure switch and burner faults are cleared by resetting the burner control unit from the control unit.
- Reset the burner control unit from the control unit.
- Restart the burner and watch for repeat faults.
Resetting all altered values to factory settings
Viessmann · HK1S and HK3S
The factory settings button resets every changed value to its default.
- Press the factory settings button to reset all altered values.
- Re-check time programs and temperatures afterwards, since they return to defaults.
Resetting coding to factory settings
Viessmann · Vitocrossal 300 CA3B Series 2.5 to 6.0
Restores the coding levels to their factory values.
- From the home screen, open Service and enter the viservice password.
- Open System coding (coding level 1) or System configuration.
- For coding level 2, enter the viexpert password.
- Select Reset coding.
Resetting operating parameters to factory settings
Viessmann · Vitocrossal 200 CM2 burner control unit
Restores all operating parameters to the delivered condition. Make sure the burner control is on standby first.
- Press S for longer than 2 seconds until the menu item flashes.
- Scroll with Y until 6 shows under Service, then press S. 6 shows under Status.
- Scroll with Y until 0 shows under Service.
- Press S. 1 shows under Status and dEL under Service.
- Press S to confirm. 1 under Service means reset, 0 means it failed.
- Press S to return to the operating display.
- Press R to reset the unit and apply settings.
Resetting saved operating data
Viessmann · Vitodens 200-W B2HA 19, 28, 35
Resets stored operating data such as hours run. The adjusted outdoor temperature is also reset to the actual value.
- Open the service level.
- Select Diagnosis, then Reset data.
- Select the required value, for example Burner starts, or All details.
Resetting scan data (burner hours, fuel use, solar)
Viessmann · Vitocrossal 300 CA3B Dual Fuel boiler
You can reset burner hours run, fuel consumption, and with a solar thermal system the solar energy yield, solar circuit pump hours and hours run output 22. All data can also be reset at once.
- From the home screen, tap Menu.
- Tap Information.
- Tap Reset data.
- Select the required data point or All details.
- Tap OK to confirm.
- Tap Confirm.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.