Reset & cancel: Boiler tips (part 4 of 8)
Short, practical technician tips on reset & cancel for boiler. Check each one against the manual for your exact model before acting.
Exit time program setting mode
Viessmann · HK1S and HK3S
You can leave the time program setting at any stage.
- Press the heating time program button; the display asks 'Exit? Yes'.
- Confirm to return to the basic display.
Exiting the service level
Viessmann · Vitodens 200-W B2HA 19, 28, 35
The service level also exits automatically after 30 minutes.
- Select Terminate service.
- Select Yes.
- Confirm with OK.
Factory reset
Viessmann · Versatronik 300 menu
The Menu has a Factory Reset item. It resets the control to factory settings, so note any custom settings first.
- Write down custom settings before resetting.
- Open Menu and select Factory Reset.
- Choose Yes to reset or No to cancel.
Factory settings button resets all values
Viessmann · Vitocontrol-S and Vitotronic 100, GC1
The factory settings button resets every changed value back to factory settings. Use it only when you intend to lose all custom settings, as nothing is kept.
- Press the factory settings button only if you want all altered values reset.
- Re-enter any site-specific settings afterwards.
Fault messages that are not rectified
Viessmann · Vitocrossal 300 CA3B
Unrectified faults can have life threatening consequences. Repeated acknowledgement hides the problem.
- Do not acknowledge fault messages several times in quick succession.
- Notify the heating contractor if a fault recurs so the cause can be analysed and rectified.
Fixed high limit trip needs manual reset
Viessmann · Vitodens 100-W WB1B
A tripped fixed high limit locks out the boiler control and must be reset by hand after the boiler has cooled.
- Let the boiler cool down before resetting.
- Reset the boiler control manually.
Gas supply fault during commissioning
Viessmann · Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0
The system can lock out during commissioning if the gas supply line has too little gas. The fault indicator lights on the control unit.
- Purge the gas supply lines again.
- Reset the burner control unit.
- Remove air from the gas line with an approved gas purge burner, or vent it outdoors.
Leave a time program early or skip a cycle
Viessmann · Vitotrol 300 remote control
Any time program setting can be ended early, and a single cycle can be skipped without changing the others.
- To end the setting, press the exit key; the display returns to the current time.
- To skip one cycle, press the skip key and move on to the next cycle.
- Once the last setting is confirmed, the display shows the current time.
Manual reset after burner lockout
Viessmann · Vitodens 200-W B2HA 45 and 60
A burner lockout after failed ignition trials requires a manual reset before the burner will run again.
- Clear the cause of the failed ignition.
- Reset the burner manually.
Menu returns to standard view after 2 minutes
Viessmann · Vitotronic 300-K (type MW2B)
If no setting is made for 2 minutes after a change, the display goes back to the standard menu.
Menu timeout returns to standard menu
Viessmann · Standard and extended menus
If no setting is made, the display returns to the standard menu automatically after 2 minutes.
- Wait 2 minutes after the last setting to return to the standard menu, or press the exit key.
Read and acknowledge faults (Vitotronic 100)
Viessmann · Vitotronic 100, GC1
Fault codes flash on the display, and the red fault lamp A flashes for all faults. Acknowledging hides the message but the lamp keeps flashing. A fault message that is not cleared by the next morning shows again. Where another LON device has a fault, it appears on the left side of the display.
- Read the fault number, fault code and LON participant number shown on the display.
- Use the up or down button to see further fault codes.
- Press the acknowledge button to hide the message. Red lamp A keeps flashing until the fault is cleared.
- To view an acknowledged fault, hold the button for about 3 seconds and select it with the up or down button.
- Use the remedy column on the fault table to fix the cause.
Redisplay an acknowledged maintenance message
Viessmann · Vitotronic 100 GC1 and Vitocontrol-S VD2/CT3/CM2
An acknowledged maintenance message can be shown again if needed.
- Press the indicated button and hold it for about three seconds.
Release a burner fault shutdown
Viessmann · CA3B Series 2.5 to 6.0
Fault shutdowns from the fan or combustion chamber air pressure monitoring can be released with the reset button R on the burner control unit, after the cause is cleared.
- Clear the cause of the fault first.
- Press the reset button R on the burner control unit.
Reset a locked burner from the home screen
Viessmann · Vitodens 100-W B1HE/B1KE
Use this to unlock a burner that is locked out by a fault. Do not reset the burner several times in quick succession.
- Select Unlock on the home screen.
- Tap OK twice to confirm.
Reset a locked burner from the submenu
Viessmann · Vitodens 100-W B1HE/B1KE
Alternative reset path through the Active messages submenu.
- Call up the home screen and open the menu.
- Select Active messages, then tap OK.
- Select Burner fault, then tap OK.
- Select Unlock, then tap OK.
- Tap OK to acknowledge the information.
- Hold the exit button for about 4 seconds to leave the menu.
Reset a tripped fixed high limit
Viessmann · Vitotronic 100 KW10B fixed high limit
The FHL can be reset by hand once it has tripped. You will hear a click if it had tripped.
- Push in the pin labelled "E" on the FHL using a ballpoint pen.
- Listen for a click to confirm the limit had tripped.
Reset after air in gas line at first start
Viessmann · Initial start-up, especially LPG
The burner may show a fault on initial start-up because of air in the gas supply, especially with LPG. The boiler uses direct spark ignition.
- Wait about 5 seconds after the fault.
- Press the R reset button.
- The ignition procedure repeats automatically.
Reset after air in the gas line at first start
Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199
Liquid propane gas lines can hold air, which causes a fault on first start.
- If a fault appears on initial start-up, wait about 5 seconds.
- Press reset button R.
- The ignition sequence repeats.
Reset after flue gas over-temperature lockout
Viessmann · Vitocrossal 200 CI2
The flue gas temperature sensor locks out the boiler if the permissible flue gas temperature is exceeded.
- Let the flue system cool down.
- Reset the burner on the programming unit.
Reset after ignition fault on first start-up
Viessmann · Vitodens 200-W B2HB 19 to 125
Air in the gas supply line, especially with LPG, can cause a fault during first start-up. The burner then ignites automatically after a safety time.
- Wait about 5 seconds after the fault appears.
- Press the R reset button to restart the ignition procedure.
Reset all altered values to factory settings
Viessmann · Vitotronic 200-H HK1S and HK3S
The factory settings button resets every value the user has changed back to the factory default.
- Press the factory settings button.
- Check the time, date and programs afterwards, since they are reset as well.
Reset all codes to factory setting
Viessmann · Vitotronic 200 and 300-K
Use this to return every coding address to its factory value. It also resets coding level 2.
- Open 'Coding level 1' in the coding menu.
- Select 'Standard setting'.
- Confirm the reset. Recheck any site-specific codes afterwards.
Reset all codes to factory settings
Viessmann · Vitotronic 300-K coding
This resets every coding address, including the ones changed in coding level 1, so record the current values first.
- Enter coding level 2.
- Select 'Standard setting' in 'Coding level 2'.
- Re-enter any site-specific values afterwards.
Reset all coding to factory default
Viessmann · Vitotronic 200-H coding
Restores the factory coding values. Key symbols were not legible in the extracted text, so keys are named by their printed letters.
- Press the w and rw keys together for about 2 seconds.
- Press D.
- Confirm 'Standard setting? Yes' with the confirm key.
- Use the up or down key to choose 'Standard setting? Yes' or 'Standard setting? No' as needed.
Reset all coding to factory setting
Viessmann · Vitodens 200-W B2HA 45, 60
Clears every coding address in coding level 1 and level 2 back to the factory defaults.
- Open Coding level 1.
- Select Standard setting.
- Confirm the reset. Level 2 codes are reset as well.
Reset all coding to factory settings
Viessmann · Vitotronic 300 GW6B control unit
Restores all coding values to the factory condition.
- From the home screen tap Menu.
- Tap Service.
- Enter the viservice password.
- Tap System coding.
- Tap Coding level 1 or Coding level 2 and enter the viexpert password.
- Tap Reset coding.
Reset all codings to factory default
Viessmann · Vitotronic 200-H, Model HK1M
Restores every coding address to its factory setting. Any custom codings are lost, so write them down first.
- Press the first and second buttons together for about 2 seconds until the first two arrows appear.
- Press the D button.
- Check the codings afterwards, because all addresses return to defaults.
Reset all codings to factory setting
Viessmann · Vitotronic 100, GC1
This resets all codings on the Vitotronic 100 to the factory values. Button symbols are not fully legible on the extracted pages.
- Press w and rw together for about 2 seconds.
- Press D.
- Confirm Base setting Yes with the confirm button.
- Select Base setting Yes or Base setting No with the up or down button.
Reset all codings to factory settings
Viessmann · Vitotronic 300 GW2 coding level 2
Resets all codings in coding level 2 to factory values. Burner type code 03 (oil-fired) cannot be reset this way.
- Press w and rw together for about 2 seconds to enter coding level 2.
- Press the menu button.
- Press OK to confirm 'Factory setting? Yes'. Select 'No' with the up or down button to cancel instead.
- Re-check the codings afterwards, as the factory values come from the boiler coding card.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.