Updated · by Aurora Star Tech Inc.

Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.

Party mode (comfort function)

Viessmann · Vitotronic 300-K

Raises room temperature for several hours without changing the normal control settings. DHW is also reheated to its set temperature and the DHW circulation pump runs if installed.

  1. Open the extended menu and select Heating.
  2. Select the heating circuit if needed.
  3. Select Party mode.
  4. Set the room temperature for party mode.
  5. To end early, set Party mode to OFF.
  6. Party mode also ends automatically when the time program switches to standard heating mode.

PC connection with ComfortSoft

Viessmann · Versatronik 200 System Control

ComfortSoft parameterisation software sets and reads all system parameters on a PC, and can graph and log values at set intervals. CoCo PC is needed for SMS error messages and remote reading of controller data.

Pipe clearance to combustible construction

Viessmann · Hot water piping near combustible construction

Non-insulated hot water pipes need a set clearance from combustible construction. Insulated pipes may use less clearance if the insulation is adequate.

  1. Keep at least 2 in. (51 mm) all around non-insulated hot water pipes from combustible construction.
  2. Insulated pipes may use 0 in. only if the insulation thickness and value are adequate.
  3. Confirm any reduced clearance against local gas codes.

Piping for the high-mass CU3A

Viessmann · Vitocrossal CU3A, all applications

A high-mass boiler does not need primary/secondary piping.

Piping layouts are conceptual only

Viessmann · Vitocrossal 200 CI2 399 to 2000

The schematics in this section are guidelines and do not show every system or safety device. Pumps shown are field supplied. Piping and components must be field verified. A low water cut-off (LWCO) is required where local codes call for it. The heating contractor is responsible for correct installation and function in the field.

  1. Verify all piping and components in the field.
  2. Install a low water cut-off where local codes require it.
  3. Confirm all pumps, which are field supplied, are sized and installed correctly.

Plug-in terminals are live when replacing the coding card

Viessmann · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

The plug-in terminals on the burner control unit stay live. Only swap the coding card after power to the burner control unit has been isolated.

  1. Isolate power to the burner control unit using the internal power disconnect inside the GW6C.
  2. Replace the coding card only after power is off.

Potable water filter service

Viessmann · Vitocrossal 300 CA3B

Filter service interval depends on filter type. Maintain high hygiene standards.

  1. On non-back-flushing filters, replace the filter element every six months and visually inspect every two months.
  2. On back-flushing filters, back flush every two months.

Power failure and saved data

Viessmann · Vitotronic 300-K MW1B

Control settings survive a power outage.

  1. No action needed. All data is saved if there is a power failure.

Power failure and seasonal changeover

Viessmann · Vitotrol 300A

Settings are kept during a power failure, and the winter/summertime changeover happens automatically.

Power isolation before servicing

Viessmann · Versatronik 502 and 502D

More than one live circuit can be present. Contact with live electrical parts can cause serious injury or death.

  1. Turn off the power supply to the control and to the damper/blower before servicing.
  2. Check the wiring diagram in the manual before working inside the unit.

Power off before servicing

Viessmann · Versatronik 585 and 585D

The unit has more than one live circuit. Turn off power to the control and to any damper or blower before servicing. Contact with live parts can cause serious injury or death. The gateway has no user-serviceable parts, and work must be done by a qualified heating contractor. Electrostatic discharge can damage the boards.

  1. Shut off power to the boiler control and any damper or blower.
  2. Check the wiring diagram in the manual before working on live circuits.
  3. Use static precautions when handling the control.

Power off before servicing; no user-serviceable parts

Viessmann · Versatronik 501 and 501D gateways

The unit has more than one live circuit. Turn off power to the control and the damper/blower before servicing. The control has no user-serviceable parts, and work should be done by a qualified heating contractor.

  1. Switch off power to the control and the damper/blower before opening the unit.
  2. Check that all circuits are dead before working inside.

Power Pump Module wiring and supply protection

Viessmann · Vitotronic 200 KW2 with Power Pump Module

Power supply must have overcurrent protection rated at most 15 A with a disconnect. The equipment must be grounded. Do not interchange the line, neutral and ground wires. Do not connect external equipment directly to the 120 VAC connectors; they are interface connections to the Power Pump Module only. Pump outputs are 120 VAC, 1 phase, 3 A max each; mixing valve motor is optional.

  1. Confirm the supply has max 15 A overcurrent protection and a disconnect.
  2. Ground the module.
  3. Check L, N and G are not swapped.
  4. Wire circulating pumps and the mixing valve motor to their marked terminals only.

Power supply and pump interface connection

Viessmann · Vitocrossal 300 CU3A boiler power supply

Electrical work must meet the code in force where the boiler is installed. Ground the appliance and bond the pipework to the building's equipotential bonding.

  1. Connect the boiler power supply at the power/pump connection interface.
  2. Refer to the wiring diagram on page 57 for connection to the control base.
  3. Bond the appliance and pipework to the building equipotential bonding.
  4. Follow NEC/ANSI NFPA 70 and local codes in the U.S.A., or CEC CSA C22.1 Part 1 and local codes in Canada.

Power supply connection

Viessmann · Vitotronic 100 KW10B

The control uses a 3-prong molded plug on a 120 VAC, 60 Hz supply. The receptacle must be dedicated to the heating system.

  1. Feed the power cord through the rear top panel wiring gate of the boiler.
  2. Slide the cable into the strain relief and tighten the set screw.
  3. Plug the cord into a receptacle reserved for the heating system only.

Power supply connection checks

Viessmann · Vitodens 200-W B2HA 45, 60

The external accessories box needs 120 VAC from a 15 A fuse-protected receptacle. Line and neutral must not be swapped, and a neutral conductor is required.

  1. Confirm 120 VAC at connector 40 on the boiler control (see wiring diagram, page 86).
  2. Confirm the supply has a neutral conductor.
  3. Do not interchange L (line) and N (neutral).
  4. Wire in Canada to CSA C22.1 Part 1 and local codes; in the U.S. use NEC ANSI/NFPA 70 and ANSI/ASME CSD-1.

Power supply for accessories and mixing controls

Viessmann · Vitodens 200-W B2HB accessories

Accessories can be powered directly from the control, and they switch with the system on/off switch. The Vitotronic 200-H HK1B mixing valve control, the mixing valve accessory kit and the Solartrol control each need their own 120 VAC supply from a wall receptacle. The programming unit can also be used in a wall-mount base accessory near the boiler.

  1. Power accessories from the control, if they are rated for it, so they switch with the system on/off switch.
  2. Give the Vitotronic 200-H HK1B, mixing valve kit and Solartrol their own 120 VAC wall receptacle supply.
  3. Mount the programming unit in the optional wall base if it is needed near the boiler.

Power supply protection and disconnect

Viessmann · Vitotronic 200-H control unit and power/pump module

The 120 VAC supply needs overcurrent protection of no more than 15 A. Viessmann recommends a disconnect switch for this supply outside the boiler room. Follow local electrical code for any fuseable disconnect.

  1. Turn off power before servicing or wiring.
  2. Fit a maximum 15 A fuse or breaker on the 120 VAC supply.
  3. Recommended: place a disconnect switch on the 120 VAC supply outside the boiler room.
  4. Install the supply per local authority requirements, or CSA C22.1 Part 1 / NEC ANSI/NFPA 70 where no local code applies.

Power supply to the control

Viessmann · All circuit diagrams

The circuit diagrams show a 120 VAC, 60 Hz supply.

  1. Install the main isolator in accordance with local regulations.
  2. Use the supply connection as shown in the wiring diagram for the chosen system.

Power switch function

Viessmann · Vitotronic 100 KW10B

In the up position the control system is on. In the down position (0) the control system is off.

  1. Switch the power switch to 0 before opening the control or working on wiring.

Power switch positions

Viessmann · Vitotronic 100 KW10B

Up (I) switches the control on. Down (0) switches the control off.

Power-off and service rules

Viessmann · Versatronik 503 NR2/Analog Bridge

Service and install work must be done by a licensed professional heating contractor. Fully isolate the electrical supply before servicing, since live components can cause shock or death. Add a disconnect switch on the 120 V supply outside the boiler room.

  1. Turn off the electric supply before any service work.
  2. Close the main gas supply valve.
  3. Lock or take other steps to stop accidental power-up during service.

Priority control during DHW tank heating

Viessmann · Heating circuits 1 to 4

With priority control on, the heating circuit target goes to 32°F (0°C) while the tank heats, the mixing valve closes and the circuit pump switches off. Without it, the circuit keeps its target. Priority is set per circuit with parameters 933.3, 934.3, 935.3 and 936.3.

Programming unit functions

Viessmann · Programming unit

Plug-in unit for setup and status viewing.

  1. Use it to set the heating program, setpoints, switching times, heating curve shift and slope, date, time, energy saving and party mode.
  2. Use it to read temperatures, operating status and faults.

Programming unit placement

Viessmann · Vitocrossal 300 CU3A

The programming unit is packed separately. It goes into the control unit support, or into an optional wall-mounting base near the boiler.

  1. Insert the programming unit into the control unit support.
  2. Or mount it in the optional wall-mounting base near the boiler.

Prolonged shutdown and clock reset

Viessmann · All operating programs

Circulation pumps can seize without power. After a prolonged or extended shutdown the date and time may need to be reset.

  1. Check the date and time after power is restored.
  2. Reset the date and time if needed (see the date and time section referenced in the manual).

Protect building surfaces from flue products

Viessmann · Vitocrossal 300 CU3A venting

Flue products can stain or damage nearby building materials in some climates. Shield exposed surfaces with corrosion-resistant material such as aluminum sheeting, attached and sealed to the building before the vent termination is installed. Vent termination on the leeward side of the building is strongly recommended.

  1. Shield or seal exposed building surfaces with corrosion-resistant material before installing the vent termination.
  2. Install the vent termination on the leeward side of the building.

Protect electronics and cable routing during install

Viessmann · Vitodens 200-W B2HA 45, 60

Keep connecting cables away from hot parts and discharge static before handling electronic modules.

  1. Route and secure cables so they stay below their maximum permissible temperature.
  2. Touch a grounded object, such as a heating or water pipe, before working on the electronic modules.
  3. Use the existing strain reliefs on the control base when securing cables.

Protect electronics and cables during wiring

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

Electronic modules can be damaged by electrostatic discharge. Cable temperature ratings must not be exceeded where cables run near hot components.

  1. Touch a grounded object, such as a heating or water pipe, before working to discharge static.
  2. Keep connecting cables away from hot components, which will damage them.
  3. Check that the cable temperature rating is not exceeded when routing and securing cables on site.
  4. Where larger cable is used, remove the existing cable grommet (up to 9/16 in.) and secure the cable with the grommet in the lower orange casing.

Protect electronics from static discharge

Viessmann · All Vitocrossal 200 CM2 units

Electronic assemblies can be damaged by electrostatic discharge.

  1. Touch a grounded object, such as a heating or water pipe, before starting work on electronics.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.