Other: Boiler tips (part 18 of 45)
Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.
Front cover must stay on during operation
Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199
Running the boiler without the front cover in place is a hazard.
- Keep the front cover in place whenever the boiler is operating.
- Reinstall the front enclosure panel after service.
Front panel controls and indicators
Viessmann · Vitotronic 300 GW2
Front panel items used during start-up: override switch, heating circuit selection, display window, normal room temperature, heating programs, adjustable high limit, fixed high limit reset button, control on/off switch, fuses, TÜV TEST button, energy saving mode, party mode, programming unit cover, green operating status indicator and red fault indicator.
- Use the heating circuit selection button before making any setting for that circuit.
- Watch the green operating status indicator for normal operation and the red fault indicator for a fault.
Front panel indicators and controls
Viessmann · Vitodens 200-W B2HA 112/150/399/530
The front panel has a red fault indicator, a green ON indicator, a reset button, the ON/OFF switch and a pressure gauge.
- Red fault indicator: lit when a fault is active.
- Green ON indicator: lit when the boiler is switched on and ready.
- Reset button: use to reset the boiler after a fault.
- ON/OFF switch: behind the black control cover, slide the cover out to reach it.
- Pressure gauge: read the heating system pressure here.
Front panel refit
Viessmann · Vitodens 100-W
The front panel is refitted by following the closing and panel instructions on page 30.
- See page 30 to refit the front panel.
Front panel ribbon cable routing
Viessmann · Vitotronic 300-K
When refitting the front part of the control, the ribbon cable must pass through the cable retaining tab so it does not pull on the connector.
- Route the ribbon cable through the retainer tab.
- Fit the front part of the control unit.
- Open the control only as described in the manual when access is needed.
Front-panel and diagnostic indicators
Viessmann · Vitotronic 100 KW10B
The control has an integrated diagnostic system with power, burner call and fault indicators, front panel AHL and FHL lights, and a flash-based sensor diagnostic LED on the KW10B. The manual does not list the flash patterns on these pages.
Frost protection and prolonged shutdown
Viessmann · Vitotronic 300 GW6C
Standby mode keeps frost protection active for the boiler and DHW tank. Circulation pumps may seize if left unpowered for long periods, so reset date and time after a prolonged shutdown.
- For each heating circuit, select the Standby mode operating program to keep frost protection active.
- If outdoor temperatures below 37°F (3°C) are expected, take frost protection measures for the heating system.
- After a prolonged shutdown, reset the date and time (see page 30).
Frost protection for the supply temperature
Viessmann · Heating circuits
Below +1°C / 34°F outdoors, the control holds the supply temperature at 15 to 22°C / 59 to 72°F (two-point control). The outdoor threshold can be changed via coding address A3.
- Check the outdoor sensor and frost threshold setting A3 if the supply is not held in the 15 to 22°C range.
Frost protection is lost when the control is powered off
Viessmann · Vitotronic 200-H HK1M
Turning the control off with the ON/OFF switch or isolating power removes frost protection for the system. Settings are kept.
- Before switching off for a long period, check whether the system must stay frost protected.
Frozen pipe protection
Viessmann · Vitodens 200-W and Vitocrossal 300 CU3A
The boiler is not designed to protect water pipes from freezing and may shut down in cold weather. If the home is left unattended in freezing weather, the water supply should be shut off and pipes drained, or a remote temperature sensor installed.
- If the home will be unoccupied in freezing weather, shut off the water supply and drain pipes.
- Add antifreeze to drain traps and toilet tanks where appropriate.
- Or install a remote temperature sensor that alerts someone to freezing conditions.
Frozen pipe risk during extended shutdown
Viessmann · Vitocrossal 300 CU3A, all models
The boiler is not designed to stop water pipes from freezing. If the building will be left unattended in cold weather, the water supply and pipes must be protected, or someone must check the building.
- Shut off the building water supply and drain the water pipes, adding potable water antifreeze to drain traps and toilet tanks.
- Or have someone check the building often during cold weather.
- Or install a reliable remote temperature sensor that alerts someone to freezing conditions.
Frozen pipe risk when boiler is off
Viessmann · Vitotronic 300-K MW2C boiler system
The boiler is not designed to prevent water pipes from freezing. If it stays off in cold weather, pipes can freeze and burst.
- If the building will be unattended in cold weather, shut off the water supply and drain the pipes, adding potable-water antifreeze to drain traps and toilet tanks.
- Or have someone check the building often, or install a remote temperature sensor that alerts on freezing conditions.
Fuel conversion from natural gas to LPG
Viessmann · Vitocrossal 200 CI2
Conversion is done with the kit. Follow the installation instructions supplied with the conversion kit.
- Follow the conversion kit installation instructions.
- Update the fuel labelling from NG to LPG.
Fuel type
Viessmann · All B2HA models
Models B2HA 80 to 100, 285 to 352 are set up for natural gas. Conversion to liquid propane is covered in the service instructions.
- Use the Service Instructions for any conversion to liquid propane.
Fuel type and conversion
Viessmann · All B2HB models
Models B2HB 19, 26, 35, 68, 94 and 125 are supplied for natural gas. Conversion to liquid propane gas is covered in the service instructions. The boiler is factory tested and calibrated, so gas valve adjustment is normally not needed at field start-up.
- Confirm the boiler is set up for natural gas before commissioning.
- For LPG, follow the conversion procedure in the service instructions.
Fuel type and factory calibration
Viessmann · Vitodens 200-W B2HB, all models
Models are for natural gas. Conversion to liquid propane needs the service instructions. The boiler is factory tested and calibrated, so gas valve adjustments are normally not needed at field start-up. Rated input is 12 to 125 MBH (3.5 to 37 kW).
- Confirm the fuel is natural gas before starting.
- For LPG, follow the conversion steps in the Service Instructions.
- Do not adjust the gas valve at start-up unless the situation requires it.
Fuel type and LPG conversion
Viessmann · Vitocrossal 300 CU3A 26 to 199
The boiler ships set for natural gas. Converting to liquid propane needs no conversion kit, but the Service Instructions must be followed.
- Confirm the boiler is set for natural gas as shipped.
- For conversion to liquid propane gas, refer to the Service Instructions.
Fuel valve and debris precautions
Viessmann · Vitorond 100 VR1
Protect the boiler during idle periods and during service.
- Keep the manual fuel supply valve shut off if the burner is idle for an extended period.
- Never burn garbage or paper in the unit, and keep combustible material away from it.
- Do not leave tools inside the combustion chamber.
- Do not tamper with the unit or controls.
Gas control knob handling
Viessmann · Vitocrossal 300 CU3A gas control
Only use the hand to push in or turn the gas control knob. Never use tools. If the knob will not move by hand, do not force or repair it; call a qualified service technician.
- Operate the gas control knob by hand only.
- If the knob will not move, call a qualified service technician.
Gas fuel and conversion
Viessmann · Vitodens 200-W B2HA 45, 60
Models B2HA 45 and 60 are for natural gas only. Conversion to liquid propane is covered in the service instructions, not in the installation instructions.
Gas odor and water-damaged appliance
Viessmann · Vitodens 200-W B2HA
Safety actions printed in the lighting instructions for gas smell and flood damage.
- Do not light any appliance if gas is smelled.
- Do not touch any electric switch or use a phone in the building.
- Leave the building and call the gas supplier from a safe location, following their instructions. If the supplier cannot be reached, call the fire department.
- Never use tools on the gas control knob. Use only hand force.
- Do not use the appliance if any part has been under water. Have a qualified service technician inspect it and replace the control system parts and gas control that were submerged.
Gas odour: what to do
Viessmann · Vitodens 200-W B2HA 19, 28, 35
Do not light anything, do not touch electric switches, and do not use a phone in the building. Call the gas supplier from outside the building. If the supplier cannot be reached, call the fire department. Do not use the appliance if any part has been under water; a qualified technician must inspect it and replace the control system and gas control parts that were wetted.
- Do not light any appliance or touch electric switches.
- Leave the building and call the gas supplier from a neighbour's phone.
- If the supplier cannot be reached, call the fire department.
- If any part was under water, have a qualified technician replace the affected control and gas control parts before use.
Gas shut-off during overheating or gas valve failure
Viessmann · Multi boiler system with Vitotronic 300-K cascade control
If the boiler overheats or the gas supply does not shut off, the pump power must stay on. Shut off the gas at a point outside the appliance.
- Do not disconnect the electrical supply to the pump.
- Shut off the gas supply at a location external to the appliance.
Gas smell or flue gas smell response
Viessmann · Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0
If gas or flue gas is smelled, the room is a danger zone. Act quickly and safely.
- Do not smoke, create sparks or flames, or operate light or electrical switches.
- Close the gas shut-off valve.
- Open windows and doors.
- Move everyone out of the danger zone.
- From outside the building, notify the gas or electricity utility.
- From a safe place outside the building, shut off the electricity to the building.
Gas type and conversion
Viessmann · WB1B-26, WB1B-35
The boiler is factory set for natural gas. A propane conversion kit is included with each boiler. Boilers are factory tested and calibrated, so gas valve adjustment is usually not needed at field start-up.
- Confirm the boiler is set for the gas type supplied.
- Use the included propane conversion kit only if the gas supply is propane.
Gas type and high altitude
Viessmann · Vitocrossal 300 CU3A 26 to 199
Lambda Pro combustion management adjusts automatically to gas type and quality, so no fuel conversion kit is required. High altitude operation up to 10,000 ft (3,000 m) uses a simple electronic adjustment.
- Check the gas supply pressure is within 4 to 14 in. w.c. for natural gas and 10 to 14 in. w.c. for LP.
- At 10,000 ft, allow for the 18 percent input de-rate.
Gas valve leakage code F E1 / F E2 - replace valve
Viessmann · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0
Both leakage codes call for replacing the combination gas valve.
- Check for gas leaks at the gauge connections before and after valve work.
- Replace the combination gas valve when F E1 or F E2 appears.
Gas valve work and leak detection
Viessmann · CA3B Series 2.5 to 6.0
Check gas fittings for tightness after any gas valve work. Leak detection spray can cause faulty operation.
- Check all gas fittings for tightness after reassembly.
- Keep leak detection spray away from electrical contacts.
Gateway board LEDs and service button
Viessmann · Versatronik 585 VI/BACIP gateway
The gateway board has a power LED, a service LED and a service button. Use the LEDs to confirm power and service state.
- Check the power LED for supply voltage.
- Check the service LED when troubleshooting the gateway.
- Use the service button as described in the full manual.
Gateway connection points (24VAC DIN rail unit)
Viessmann · Versatronik 501D DIN rail unit
The DIN rail unit has four connection points: the RJ45 control connection, the paralleled BUS connection, the LON terminals A and B, and the 24VAC power input.
- Connect the RJ45 cable to the control.
- Use the paralleled BUS connection where more than one gateway is used.
- Wire the LON network to terminals A and B.
- Connect 24VAC power.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.