Updated · by Aurora Star Tech Inc.

Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.

Example: outdoor temperature raises the reduced room set-point (F8:-5, F9:-14)

Viessmann · Vitotronic 200-H, Model HK1M

With an outdoor sensor, the reduced room set-point rises as outdoor temperature falls. Example: reduced room set-point 3°C / 37°F, normal room set-point 20°C / 68°F. The raise starts below -5°C / 23°F (F8) and reaches normal room temperature at -14°C / 7°F (F9).

  1. Check that F8 is -5 and F9 is -14 (factory defaults).
  2. Confirm the reduced set-point (3°C / 37°F) and normal set-point (20°C / 68°F) are as expected.
  3. Watch the room set-point climb along the heating curve between the two outdoor limits.

Exhaust vent pipe material

Viessmann · Exhaust vent pipe

Only ULC S-636 / UL 1738 listed vent material may be used for the exhaust vent pipe.

  1. Check the vent pipe label for ULC S-636 / UL 1738 before installing the exhaust.

Expert level menu groups

Viessmann · Versatronik 200 System Control expert level

The expert level menu is organised into these groups: Configuration, Heat source, Cascade, Tank, Slab curing, 0-10 I/O, DHW, Heating circuit 1, Heating circuit 2, Solar / MF, and Cooling operation. Subgroups include bus ID, boiler type, sequencing, hysteresis, voltage curves, DHW pump function, mixing valve timing, and solar protection parameters. Parameter values are not printed on these pages.

  1. Open Main Menu, then Expert level.
  2. Select the group that matches the component to set.
  3. Refer to the parameter table in the manual for the correct values.

Expert menu branches (menu map)

Viessmann · Versatronik 200 Expert menu

The Expert level menu is split into branches for heat source, cascade, buffer tank, 0-10/slab curing/DHW, two heating circuits, solar/MF and Expert Level IM. The menu map pages show only the branch headings. The individual settings are in diagram form and cannot be read from the text.

  1. Open the Main Menu, then go to the Expert level.
  2. Choose the branch that matches the equipment: Heat Source, Cascade, Buffer Tank, 0-10/Slab Curing/DHW, Heating Circuit 1, Heating Circuit 2, Solar/MF or Expert Level IM.
  3. Check the full menu diagram in the manual for the exact settings in each branch.

Extended and standard menu layout

Viessmann · Vitotronic 300-K

The extended menu holds Information, Fault, Solar energy, Test mode, Boiler sequence, Economy and Party modes, plus the heating and DHW program groups. The standard menu holds Settings, Time/Date, Language, Contrast, Brightness, Temperature unit, Name for heating circuit and Holiday program.

  1. Use the menu overview on p. 40 to find each function before adjusting it.

Extended menu structure

Viessmann · Vitocrossal 300 CU3A with Vitotronic 200 KW6B

Top-level groups of the extended menu are Heating, DHW, Information, Settings, Test mode and Solar energy. Settings include time and date, language, contrast, brightness, temperature unit and heating circuit names. Heating covers room temperature and operating program settings, time programs, holiday program, heating curve and zone circuits. DHW covers DHW temperature and time programs.

  1. Use the overview to find the menu group you need.
  2. Check the Heating, DHW and Settings groups for the setting to change.

External 0-10 V DC signal connection

Viessmann · Vitodens 222-F, B2TB 19, 35, 68, 125

The external 0-10 V DC signal connects to the plug labelled 0-10VDC in the external connection accessory box. The manual refers to a chart for maximum boiler water temperature versus signal, but that chart is not on the pages supplied.

  1. Connect the external 0-10 VDC signal to plug 0-10VDC in the external connection accessory box.
  2. Make sure the polarity is correct.
  3. Use the manufacturer's chart for the maximum boiler water temperature and required signal.

External accessory connection box wiring

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

The external accessory connection box takes a 0-10V input for accessories such as a Vitotrol remote or a mixing valve, and the pump. Power is 120/1/60, 12 A full load amperage, supplied through a disconnect and protection. Wiring must follow the NEC/ANSI NFPA 70 in the USA and the CEC CSA C22.1 Part 1 in Canada, plus local codes. See the wiring diagram on p. 47 for connection to the control base.

  1. Provide power supply at 120/1/60 with a disconnect and overcurrent protection, rated for 12 A full load.
  2. Connect the 0-10V input for accessories as required.
  3. Connect the pump.
  4. Follow NEC or CEC and local electrical codes.

External contacts must be potential-free

Viessmann · Vitotronic 300 GW6B

Live contacts on the aVD, aBÖ and similar inputs cause short circuits or phase failure.

  1. Confirm each external contact is dry (potential-free) before connecting.
  2. Use normally closed contacts for safety chains at plug aBÖ.

External potential-free contacts on 24 VAC thermostat terminals

Viessmann · Vitotronic 100 KW10B

Room thermostats or other potential-free contacts, such as a zone valve end switch, connect to the 24 VAC thermostat terminals. Contacts must have adequate insulation clearance to live parts and must be certified for this application.

  1. Confirm the contact has sufficient insulation clearance to live parts.
  2. Confirm the contact is certified for this application before connecting it to the thermostat terminals.

External safety and disable connections

Viessmann · Vitotronic 100 GC1 line voltage motherboard

Jumpers on the line voltage motherboard must be removed before external safety equipment or an external disable is wired in.

  1. Remove the jumper at terminal a before connecting external safety equipment.
  2. Remove the jumper at terminal b before connecting an external disable.
  3. Connect the external burner activation at terminal c as needed.

Factory default time programs

Viessmann · Vitotronic 200-H HK1S and HK3S

Factory default: heating at normal room temperature from about 6:00 to 22:00, domestic hot water from about 5:30 to 22:00 if a DHW tank is fitted, and reduced room temperature with frost protection at 3 C (37 F) from 22:00 to 6:00. Date and time are preset and change for winter and summer time automatically.

Fault code variables on the gateway

Viessmann · Versatronik 501 gateway fault variables

Boiler 1 to 4 and zone/cascade fault code points carry the Appendix A fault code. Relay state points carry the Appendix B state.

Fault codes are shown in hexadecimal

Viessmann · Versatronik 300 cascade control

The control shows fault codes in hex to save screen space. The base format shown on a BMS depends on the BMS software. The manual gives Niagara AX examples: a mask on a numeric bit-and object shows the hex value, and a numeric-to-enum conversion maps the codes to text.

  1. Check the hex code in the fault table (column 1) against the display.
  2. Use the decimal column when the BMS shows base 10.

Fault display format

Viessmann · Vitotronic 200 KW2

A fault on the display shows plain text or a fault code, a fault number from 1 to 10, and a fault symbol. Faults shown in plain text include burner, fixed high limit, safety circuit, outdoor sensor, supply sensor, DHW tank sensor, return sensor, room sensor and flue gas sensor. The fixed high limit, safety circuit and flue gas sensor only show with the fault indication module accessory.

Fault indication module

Viessmann · Fault indication and Switching Module-V

Faults show on the display and trigger the central fault output on the Switching Module-V accessory.

Fault memory

Viessmann · Vitocrossal 200 CI2

The 10 most recent faults are saved. The newest code is shown first, followed by earlier codes. If the burner restarts repeatedly on a non-lockout fault without a code, the fault memory may show the cause.

  1. Open the fault memory to read the last 10 faults.
  2. Check the newest code first, then the earlier codes.

Fault messages: acknowledge and recall

Viessmann · Vitodens 200-W and Vitocrossal 300 CU3A

A fault flashes the fault symbol and shows "Fault", and the red fault indicator flashes. Acknowledging stops the flashing but the fault message returns the next day if the fault is not fixed. Signalling equipment such as a buzzer is switched off on acknowledgement.

  1. Note the fault code and give it to the heating contractor.
  2. Acknowledge the fault with OK.
  3. To recall an acknowledged fault, tap OK for about 4 seconds, or use the extended menu and select "Fault".
  4. If there are several faults, scroll through them with the arrow keys.
  5. For the meaning of fault codes, refer to the Vitodens 200-W and Vitocrossal 300 CU3A Service Instructions.

Fault reporting in GW6B lead and lag system

Viessmann · Vitotronic 300 GW6B cascade

The lead boiler shows its own faults. The gateway does not pass lag boiler faults to the BMS as lead faults, but it reports each boiler fault on its own boiler fault point.

  1. If the physical control shows a fault but the gateway does not report it, check the fault point for the boiler that has the fault.
  2. Boiler 1 fault point shows only faults from the lead boiler (boiler 1).

Fault search and acknowledging a fault (Vitocontrol-S)

Viessmann · Vitocontrol-S VD2/CT3/CM2

The programming unit shows the fault in plain language and as a fault code. Acknowledging stops the lamp flashing only for that fault and the fault message comes back at 7:00 the next day if it is still present.

  1. Open the hinged cover on the programming unit.
  2. Press the fault search button. The error source appears in plain language and as a fault code.
  3. Press the next key until the display shows 'Acknowledge? Yes'.
  4. Use the arrow keys to choose Yes or No.
  5. Press confirm. The display returns to the boiler temperature.
  6. Close the hinged cover on the programming unit.
  7. To view an acknowledged fault again, press the fault key for about 2 seconds. Use the arrow keys to scroll if two or more faults exist.

Fault system behavior definitions

Viessmann · Vitodens 200-W B2HB 19 to 35, 68 to 125

The fault tables use three behavior terms: control mode, burner in fault mode, and burner blocked.

  1. Control mode: boiler and burner stay fully operational. The fault code must still be verified and reset.
  2. Burner in fault mode: boiler control needs a manual reset (reset button R) before the burner can run again.
  3. Burner blocked: the burner resumes operation once the fault cause is corrected.
  4. Some codes stay on factory default settings (control mode with factory default) until the part is fixed.

Field cabling and routing requirements

Viessmann · Vitodens 200-W B2HB field wiring

Cables required in the field include the outdoor sensor, mixing valve control, mixing valve kit, remote operating mode switching, remote disable, alarm output, wall-mount base and circulating pump. Route cables as illustrated so the control unit can move freely. Do not secure cables to the control unit bracket. Keep cable temperatures within their rated limits.

  1. Run cables as shown in the installation illustration so the control unit moves freely.
  2. Do not clamp cables to the control unit bracket.
  3. Check that cable temperature ratings are not exceeded where cables are routed and secured.
  4. Only one accessory or switch contact may be connected to a plug contact at a time.
  5. Read the accessory's own installation instructions for other required steps.

Field cabling needed for accessories

Viessmann · Vitocrossal 300 CU3A boiler accessories

These accessories need field cabling to the boiler control. Only one accessory or one switch contact can be connected to a plug contact at a time.

  1. Cable the outdoor temperature sensor.
  2. Cable the Vitotronic 200-H and HK1B mixing valve control.
  3. Cable the accessory kit for a heating circuit with mixing valve.
  4. Cable remote switching of operating mode.
  5. Cable remote disable.
  6. Cable the alarm output.
  7. Cable the wall-mount base.
  8. Cable the circulating pump.
  9. Cable the zone circuit thermostats.

Field contact requirements for digital inputs

Viessmann · Extension EA1 digital inputs

External contacts must be floating (dry). Observe safety category II: 8.0 mm air and creep path, or 2.0 mm insulation thickness to live parts.

  1. Use floating contacts only on DE1 to DE3.
  2. Keep the required clearances to live parts when wiring.
  3. For brief DHW recirculation pump operation, use a pushbutton contact on DE1, DE2 or DE3 and set the runtime with coding address 3D.

Field modifications void CSA certification

Viessmann · Versatronik 503 NR2/Analog Bridge

Changing this control panel in the field cancels the factory CSA certification. If you modify it, an electrical safety field inspection is required under local codes. Viessmann is not responsible for damage from field modifications.

Field wiring to digital inputs and low-voltage outputs

Viessmann · EA1 extension module and external connections

Keep the separation required for external contacts and the 0-10 V input.

  1. For external contacts, observe safety category II: 8.0 mm air gap and creep path, or 2.0 mm insulation thickness against live parts.
  2. Ensure DC separation between the LV output and the earth conductor of the on-site voltage source when using the 0-10 V input.

Field-supplied controls and OpenTherm

Viessmann · Terminal strip for accessories, OpenTherm, outdoor sensor

Field-supplied operating controls connect to the terminal strip for accessories. Follow the installation instructions of those controls. OpenTherm is a point-to-point link between the boiler and a room controller that sends a heat demand (water temperature request). The Viessmann Input Module accepts a 0-10 VDC modulating signal from a boiler reset controller and sends it to the Vitodens 100 over OpenTherm.

  1. Wire the field outdoor temperature sensor and OpenTherm connections to the terminal strip as shown in the manual.
  2. Follow the field controls' installation instructions.

Find active faults and service messages

Viessmann · Vitodens 100-W B1HE/B1KE

Active messages appear in the main menu when a fault, warning or service message is present. Faults and warnings are sorted into their own entries, and the message history is kept under Information.

  1. Open the main menu from the home screen.
  2. Select Active messages or Faults and Warnings.
  3. Tap Acknowledge to clear a fault or service message that is listed.
  4. Check Information > Message history for earlier messages.

Find the serial number before ordering parts

Viessmann · Vitodens 222-F B2TB 19, 35, 68, 125

Parts orders need the 16-digit boiler serial number from the bar code label, or the 12-digit ASME/NB serial. Serial 7542250 applies to B2TB 19 and 68; serial 7542251 applies to B2TB 35 and 125. Some parts are not reverse compatible with earlier versions, so always quote the serial.

  1. Remove the front enclosure panel to reach the serial number location.
  2. Note the 16-digit bar code serial or the 12-digit ASME/NB serial.
  3. Quote the serial when ordering replacement parts.

Finding and acknowledging faults on the 300-K

Viessmann · Vitotronic 300-K MW1S

Fault numbers are shown as a consecutive number (1 to 10) with a code. The red fault lamp flashes for all faults.

  1. Press the fault button to show the fault.
  2. Scroll through further fault codes with the arrow buttons.
  3. Acknowledge a fault with the acknowledge button. The message hides but the red lamp keeps flashing.
  4. To view acknowledged faults, press and hold the button for about 3 seconds, then select with the arrow buttons.
  5. An unacknowledged fault returns the following morning if it is not cleared.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.