Commissioning: Boiler tips (part 10 of 21)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on commissioning for boiler. Check each one against the manual for your exact model before acting.

Flush retrofit piping before connecting the boiler

Viessmann · Retrofit installations of Vitocrossal 200 CI2

On retrofit jobs, old piping can carry sludge that restricts flow and damages the boiler. Damage from this is not covered under warranty.

  1. Before connecting the boiler, flush previously used piping with city pressure water at 50-60 psi.
  2. Consider installing magnetic filtration; Viessmann recommends it.

Frost protection with the standby program

Viessmann · Vitocrossal 300 CA3B

With frost protection monitoring, select Standby mode on every heating circuit. Central heating and DHW heating stop, but frost protection for the boiler and DHW tank stays active. Outdoor temperatures below 37°F (3°C) need frost protection measures for the system.

  1. For every heating circuit, select the Standby mode operating program.
  2. If outdoor temperatures below 37°F (3°C) are expected, take frost protection measures or call the heating contractor.

Fuel conversion to liquid propane

Viessmann · Vitodens 222-F B2TB 19, 35, 68, 125

The boiler ships set for natural gas. Converting to liquid propane does not need a conversion kit, but the fuel type must be changed in the start-up procedure.

  1. Use the Convert Fuel Type to Liquid Propane Gas procedure (see p. 18 of the manual).

Gas and CO2 measurement before and after gas work

Viessmann · Vitocrossal 200 CI2

A CO2 measurement is required before and after working on gas appliances.

  1. Take a CO2 reading before starting work on the gas system.
  2. Take a CO2 reading again after the work is finished.

Gas connection components before the boiler

Viessmann · Vitodens 200-W B2HA 45, 60

Install a ground joint union, a capped drip leg and a manual equipment shutoff valve ahead of the boiler gas connection. Valves must be listed by a nationally recognized testing agency. Tag the shutoff valves and show the operator where they are.

  1. Fit the ground joint union, capped drip leg and manual shutoff valve as shown in the manual.
  2. Use only listed valves.
  3. Make the boiler gas connection (1 in. NPT).
  4. Put a tag on each shutoff valve and brief the owner on them.
  5. Consider an external safety solenoid valve for LPG where the boiler is below grade.

Gas leak test and gas work safety

Viessmann · Gas line work

Test for leaks with soap and water. Keep open flames out of the room. Never purge gas into the combustion chamber.

  1. Make sure there is no open flame in the room.
  2. Never use matches, candles or flames to check for leaks.
  3. Apply soap and water solution to joints and check for bubbles.
  4. After any gas work, run a gas leak test.

Gas leak test and purge

Viessmann · Vitodens 200-W B2HA 45, 60

Use an approved liquid leak-detection spray. Keep it off electrical parts, wires and connectors, and away from the gas valve regulator and regulator vent opening. Never check for leaks with an open flame.

  1. Spray approved leak solution on all joints and fittings.
  2. Keep spray off electrical components, wires and connectors.
  3. Keep spray away from the regulator and the regulator vent opening.
  4. Fix any leaks found and retest.
  5. Purge air from the gas line before lighting.

Gas piping pressure test isolation

Viessmann · Vitodens 200-W B2HA 45, 60

At test pressures of 1/2 psig (14 in. w.c.) or less, the boiler can stay connected but must be isolated by its manual shutoff valve. At higher test pressures, the boiler and its shutoff valve must be disconnected from the piping. Overpressure to the boiler gas regulator or gas valve voids the warranty.

  1. At 1/2 psig (14 in. w.c.) or less, close the boiler's manual shutoff valve to isolate it.
  2. Above 1/2 psig (14 in. w.c.), disconnect the boiler and its shutoff valve from the gas piping.
  3. Never expose the gas regulator or gas valve to extreme test pressure.

Gas supply piping recommendations

Viessmann · Vitocrossal 200 CI2 399 to 2000

Gas train layout and regulator requirements for the boiler supply.

  1. Install one gas pressure regulator per boiler.
  2. Use a regulator with an outlet size equal to the boiler fuel connection; use a concentric reducing coupling if the pipe diameter changes.
  3. Install a ground joint union, capped drip leg and manual shutoff valve before the boiler connection; valves must be listed by a nationally recognized testing agency.
  4. Install a gas filter if the gas pipe may contain dirt.
  5. Design piping so it does not interfere with serviceable components.

Gas supply pressure limit and fuel type

Viessmann · Vitodens 222-F B2TB, natural gas and liquid propane

Maximum gas supply pressure is 14 in w.c. The boiler is factory set for natural gas. Switching to liquid propane needs no conversion kit. The factory gas valve is set and normally needs no field adjustment.

Gas supply sizing and pressure drop

Viessmann · Vitodens 200-W B2HA 45, 60

Gas piping must be sized from pipe length, fittings, gas type and the total input of all gas appliances in the building. There must be no noticeable pressure drop when any appliance (or combination) lights or runs. Maximum gas supply pressure is 14 in. w.c. Design the layout so piping does not block serviceable components.

  1. Size the gas line using CAN/CSA B149.1 and .2, or NFPA 54 / ANSI Z223.1, plus local codes.
  2. Confirm the line can carry the total input of all appliances in the building.
  3. Check that no pressure drop is seen when appliances light or run.
  4. Do not exceed 14 in. w.c. gas supply pressure.

Gas type and gas valve setup

Viessmann · Vitocrossal 300 CU3A

Boiler is factory set for natural gas. Converting to liquid propane needs no kit. Gas valve is factory calibrated and usually needs no field adjustment.

  1. Confirm the fuel is natural gas or liquid propane as installed.
  2. Do not adjust the gas valve at field start-up unless required.

Gas type and natural gas to LPG conversion

Viessmann · Vitocrossal 300 CU3A, natural gas and liquid propane

Lambda Pro adjusts automatically to gas type and quality, so no fuel conversion kit is needed for normal gas type changes. For a field conversion from natural gas to liquid propane, use the NG>LPG label kit included in the boiler literature set.

  1. Confirm gas type on site before startup.
  2. For a field conversion to LPG, use the NG>LPG kit and follow its included instructions and labels.
  3. Boiler is factory set for natural gas.

Gas type and propane conversion

Viessmann · Vitodens 100-W WB1B

Boiler ships factory set for natural gas. A propane conversion kit comes with each boiler. Factory gas valve settings are tested, so field gas valve adjustment is normally not needed at start-up.

  1. Confirm the boiler is set for the gas type being supplied before start-up.
  2. If the site uses propane, install the included propane conversion kit.

Gas type changes do not need a conversion kit

Viessmann · Vitodens 200-W B2HB

Lambda Pro combustion control adjusts automatically to the gas type and quality, so no fuel conversion kit is needed. The unit is delivered preset for natural gas.

  1. Confirm supply gas is within the minimum and maximum pressure ratings for the gas type.
  2. Do not install a conversion kit for LPG operation.

Gas valve and fuel conversion

Viessmann · Vitodens 222-F, B2TB 19, 35, 68, 125

The boiler ships set for natural gas. Converting to liquid propane needs no conversion kit. The boiler is factory-tested and calibrated, so gas valve adjustment is not normally needed at field start-up.

  1. Confirm the boiler is set for the fuel being used.
  2. Do not adjust the gas valve at field start-up unless testing shows it is needed.

Gas valve and ignition protection

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

Gas valve is factory set. Protect the ignition components from water during operation and service.

  1. Do not expect to need gas valve adjustment at field start-up; the boiler is factory-tested and calibrated.
  2. Install the boiler so the gas ignition components are protected from spraying or splashing water.

Gas valve factory setting

Viessmann · Vitocrossal 300 CU3A 26 to 199

The boiler is factory tested and calibrated, so gas valve adjustments are usually not needed at field start-up.

  1. Do not adjust the gas valve at field start-up unless the instructions require it.

Gas valve factory setting and model selection

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

The boilers are factory tested and calibrated, so gas valve adjustment is usually not needed at field start-up. Boiler size must come from an accurate building heat loss calculation and must suit the connected radiation.

  1. Confirm the boiler size against a heat loss calculation of the building.
  2. Confirm the connected radiation suits the selected boiler.
  3. Do not adjust the gas valve at start-up unless it is required.

Gas valve is factory set

Viessmann · Vitodens 200-W B2HA 45, 60

The boiler is factory tested and calibrated. Gas valve adjustment is normally not needed at field start-up.

Gateway mounting options

Viessmann · Versatronik 505 and 505D

The gateway can be part of a control panel or a stand-alone device. It translates between the listed boiler controls and BACnet IP DDC systems.

Hand over documentation and operator instruction

Viessmann · Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0

The system manufacturer must instruct the system operator on operation and maintenance and hand over the documents.

  1. Complete the customer information file and split it into the operator segment and the heating contractor segment.
  2. Give the operator segment to the system operator and keep the contractor segment on file.
  3. Assemble all parts lists, operating and service instructions into one file and give it to the system operator.
  4. Include instruction on maintenance work and any installed accessories, such as remote controls.

Hand over the system to the owner

Viessmann · Vitodens 200-W B2HA 19, 28, 35

The installer must make the system operator or owner familiar with the system before leaving.

  1. Explain the proper operating sequence of the system.
  2. Explain the equipment.
  3. Demonstrate an emergency shut-down, and explain what to do and what not to do.
  4. Explain that proper maintenance is required for safe operation.
  5. Explain the need for professional service every year before the heating season begins.
  6. Leave the documentation in a readily accessible place near the boiler.

Hand over the system to the user

Viessmann · Vitodens 200-W B2HB 19 to 35, 68 to 125

After installation, the installer should give the operating instructions to the system user and show them how to run the system.

  1. Give the operating instructions to the system user.
  2. Instruct the user on operating the system.

Hand over to the system user

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

The installer must give the operating instructions to the system user and show them how to operate the system. Labels on the boiler surfaces must be kept and read. Contact Viessmann for any replacement labels.

  1. Give the operating instructions to the system user.
  2. Instruct the user in operating the system.
  3. Do not remove any safety labels or stickers on the boiler; order replacements from Viessmann if needed.

Handover and annual service

Viessmann · Vitotrol 300A installations

Once installation is complete, the contractor must review the system with the owner. Documentation should be kept near the boiler.

  1. Explain all equipment, safety requirements and the shutdown procedure to the owner.
  2. Explain the need for professional service every year before the heating season.
  3. Leave the product documentation near the boiler for service personnel.

Handover and start-up checks

Viessmann · Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0

Initial start-up must be done by a qualified heating contractor, who also completes the maintenance record. The contractor must confirm the field-supplied controls work before handover.

  1. Check the field-supplied low water cut-offs, staging controls, pumps, motorized valves, air vents and thermostats.
  2. Brief the owner on system operation, the combustion air need, emergency shutdown, and that maintenance is required.
  3. Complete the Maintenance Record on page 158.

Handover to owner

Viessmann · Vitocrossal 300 CA3B Series 2.5 to 6.0

The heating contractor must review the system with the owner after installation.

  1. Review all equipment, safety precautions, and shutdown procedure with the owner.
  2. Explain the need for professional service every year before the heating season begins.
  3. Store the literature (installation, service and operating instructions) near the boiler.

Handover to the system operator

Viessmann · Vitocrossal 300 CA3B Dual Fuel

The installer must show the operator how the system works, how to start and shut it down, and the need for annual professional service before the heating season.

  1. Explain normal operating sequence and the need for combustion air.
  2. Demonstrate emergency shutdown and what not to do.
  3. Explain that proper maintenance is required for safe operation.
  4. Complete the Maintenance Record (page 158 of the manual).

Handover to the system user

Viessmann · Models 45, 60

Before leaving the site, the installer should hand over the operating instructions and show the user how to run the system.

  1. Give the operating instructions to the system user.
  2. Instruct the user in operating the system.
  3. Follow the safety instructions on all labels attached to the boiler and do not remove them. Contact Viessmann for replacement labels.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.