Short, practical technician tips on commissioning for boiler. Check each one against the manual for your exact model before acting.

Control installation checklist

Viessmann · Versatronik 200 System Control

Order of work for installing the Versatronik 200 control, from unboxing through coding and testing.

  1. Review the box contents.
  2. Mount the control on a solid surface using field-supplied hardware.
  3. Wire and connect the outdoor temperature sensor.
  4. Wire and connect the LLH/common supply temperature sensor.
  5. Wire and connect the DHW temperature sensor.
  6. Wire the boiler as required by the system (demand and communication connections, including the CoCo OT device).
  7. Wire the 120 VAC pumps (DHW, mixing valve heating circuit and multifunction).
  8. Wire the mixing valve (multifunction).
  9. Wire Lago remotes if used (accessory).
  10. Wire the input demand/signal as the system requires.
  11. Code and test the system.

Control requirement to prevent flue gas condensation

Viessmann · Vitorond 200 VD2A with Vitotronic control

The boiler must be run through the Vitotronic Therm-Control logic to prevent flue gas condensation at all local return water temperatures. Other control options need approval from a Viessmann technical representative.

  1. Confirm the Vitotronic control with Therm-Control logic is installed.
  2. Confirm the Therm-Control sensor is in place on the boiler return casting.
  3. Contact Viessmann before using any other control option.

Convert from natural gas to liquid propane

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

Field conversion of the gas valve and coding to liquid propane. Apply the supplied conversion labels when finished.

  1. Set adjusting screw A at the gas valve to "2" using a 2.5 mm hex key.
  2. Switch ON/OFF switch 8 to ON. Slide the black control cover out to reach it.
  3. Enter coding level 2 and open "General".
  4. Set coding address 11 to 9.
  5. Set coding address 82 to 1 for liquid propane.
  6. Return to coding address 11 and set any value except 9.
  7. Exit coding level 2 and open the gas shut-off valve.
  8. Apply the supplied fuel conversion labels.

Customer handover

Viessmann · All Vitodens 200-W B2HA installations

The installer must give the operating instructions to the system user and show them how to operate the system.

  1. Hand over the operating instructions.
  2. Show the system user how to operate the system.

DHW circulating pump direction

Viessmann · Vitodens 200-W B2HA 45, 60 DHW circulation piping

In the piping layouts, the DHW circulating pump must pump into the boiler, not away from it. This applies to every layout shown.

  1. Pipe the DHW circulating pump so it pumps into the Vitodens boiler, as shown in the layout for the system.
  2. Check the pump label letter against the legend for the chosen layout.

DHW piping and tank requirements

Viessmann · Vitodens 200-W B2HB with DHW tank

DHW supply and return piping between the boiler and the Viessmann DHW tank must be at least 1¼ in. For non-Viessmann tanks, calculate the coil pressure drop against the pump residual head. Undersized DHW piping can cause short-cycling and poor DHW supply.

  1. Run DHW supply and return piping at least 1¼ in. between boiler and tank connections.
  2. For a non-Viessmann tank, calculate the tank coil pressure drop against the field pump residual head.
  3. Verify the Viessmann DHW tank sensor operates correctly with a non-Viessmann tank, per the tank manufacturer.
  4. Install a temperature tempering valve in the DHW supply line (strongly recommended).

DHW piping size

Viessmann · Vitodens 200-W B2HA 80-100, 285-352

DHW supply and return piping between the boiler and the tank connections must be at least 1 1/4 in. pipe. Smaller piping can cause boiler short-cycling and poor DHW supply.

  1. Use at least 1 1/4 in. pipe for DHW supply and return to the tank.

DHW piping size and flow for tank applications

Viessmann · Vitocrossal 300 CU3A with DHW storage tank

DHW supply and return piping must be sized so the field pump has enough head to push water through the tank coil and the boiler heat exchanger. Undersized piping can cause short-cycling and poor DHW supply.

  1. Use at least 1¼ in. pipe between the boiler DHW connections and the Viessmann DHW tank connections.
  2. With a non-Viessmann tank, calculate the tank coil pressure drop against the field pump's residual head.
  3. Confirm enough flow reaches the boiler heat exchanger.

DHW piping size and flow with non-Viessmann tanks

Viessmann · Vitodens 200-W B2HA 45, 60 DHW installations

DHW supply and return piping between the boiler and the tank must be at least 1¼ in. so the field pump's residual head is used well. A non-Viessmann tank needs a coil pressure drop check against the pump head. Undersizing can cause short-cycling and poor DHW supply.

  1. Install DHW supply and return piping of at least 1¼ in. between boiler DHW connections and the Viessmann tank connections.
  2. For a non-Viessmann tank, calculate the tank coil pressure drop against the boiler pump residual head.
  3. Confirm enough water flow reaches the boiler heat exchanger before commissioning.

DHW piping size between boiler and tank

Viessmann · DHW tank piping

Piping between boiler DHW connections and the Viessmann DHW tank connections must be at least 1¼ in. This lets the field pump's residual head overcome the DHW coil and still feed the boiler heat exchanger. Undersized piping can cause short-cycling and weak DHW supply.

  1. Run DHW supply and return piping at a minimum of 1¼ in. between the boiler and the tank.
  2. Confirm pump residual head covers the tank coil and boiler heat exchanger flow.

DHW pump connection

Viessmann · Vitotronic 100 KW10B

The KW10B can run a DHW pump when OT or DHW set point function is on. The pump is a 120 VAC, 3 A full load pump on output 21 at the LGN terminals. Pump operation follows the DIP and dial switch settings.

  1. Connect the 120 VAC DHW pump (max 3 A) to the LGN terminals of output 21.
  2. Set DIP and dial switches for the required DHW pump operation.

DHW sensor installation

Viessmann · Vitotronic 100 KW10B

Install the DHW sensor in the tank well as the tank manufacturer instructs. DHW function must be enabled in the start-up section.

  1. Install the DHW sensor in the tank well following the tank maker instructions.
  2. Connect the DHW sensor wires to connector X6 terminals 5.1 and 5.2.
  3. Enable DHW function as described in the start-up section.

DHW sensor on a non-Viessmann tank

Viessmann · Vitocrossal 300 CU3A 26 to 199

With a non-Viessmann tank, the installer must check the sensor works correctly with the tank maker. A temperature tempering valve is strongly recommended in the DHW supply line.

  1. Confirm sensor operation with the original tank manufacturer.
  2. Install a temperature tempering valve in the DHW supply line.

DHW tank piping and non-Viessmann tanks

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

DHW supply and return piping between the boiler and a Viessmann DHW tank must be at least 1 1/4 in. For non-Viessmann tanks, calculate the DHW coil pressure drop against the field supplied pump residual head to confirm enough flow reaches the boiler heat exchanger. Insufficient flow can cause short cycling and poor DHW supply. If a tank other than a Viessmann Vitocell 100 or 300 is used, verify the Viessmann DHW sensor operation with the tank manufacturer. A temperature tempering valve in the DHW supply line is strongly recommended.

  1. Use at least 1 1/4 in. piping between the boiler DHW connections and the Viessmann tank.
  2. For non-Viessmann tanks, calculate the coil pressure drop against pump residual head.
  3. Verify DHW sensor operation with the original tank manufacturer.
  4. Install a temperature tempering valve in the DHW supply line.

DHW tank piping and pump check

Viessmann · DHW tank installations

Undersized DHW piping or a pump with too little head can cause short-cycling and poor DHW supply. Non-Viessmann tanks need a coil pressure drop check against pump head.

  1. Size DHW supply and return piping to the minimum pipe size for the model.
  2. On non-Viessmann tanks, calculate DHW coil pressure drop against the field pump's residual head.
  3. Confirm the tank sensor with the tank maker if the tank is not Viessmann Vitocell 100 or 300.
  4. Install a temperature tempering valve in the DHW supply line.

DHW timer for continuous availability

Viessmann · Applications 3 and 4

If DHW production should be possible at any time, the timer schedule must cover the full day.

  1. Set the DHW timer schedule as desired.
  2. For DHW available at any time, program the timer to 0:00 to 24:00.

Direct vent gasket selection

Viessmann · Direct vent installations

Direct vent combustion air gaskets can be swapped. One is sized for 3 in. (89 mm) OD CPVC/PVC/ABS pipe, the other for 3 in. (80 mm) OD PP(s) pipe.

  1. Match the gasket to the combustion air pipe material.
  2. Use the 89 mm gasket for CPVC/PVC/ABS.
  3. Use the 80 mm gasket for PP(s).

Do not use Teflon tape or compression fittings on oil lines

Viessmann · Oil piping at the burner and fuel unit

Teflon tape can cause oil valves to fail. Compression fittings are not allowed on the oil piping. Use non-hardening pipe joint compound on all threads.

Domestic hot water limit when the system uses a DHW tank

Viessmann · Vitotronic 100 GC1 with domestic hot water tank

If the system is run with a domestic hot water tank, the maximum permissible DHW temperature must not be exceeded. Install a suitable safety device if needed.

  1. Check the maximum permissible domestic hot water temperature.
  2. Install a suitable safety device if the limit could be exceeded.

Domestic hot water tank sensor and tempering valve

Viessmann · Vitodens 200-W B2HA 45, 60

For a Vitocell 100 or 300 tank, mount the DHW temperature sensor in its well per the tank instructions. For any other tank, the installer must check sensor operation with the tank maker. Viessmann strongly recommends a temperature tempering valve in the DHW supply line.

  1. Locate the DHW sensor well on the Vitocell tank and install the sensor per the tank instructions.
  2. For a non-Viessmann tank, confirm sensor operation with the tank manufacturer.
  3. Install a temperature tempering valve in the DHW supply line.
  4. Apply thread sealant to the DHW connections.

Drip pocket clearance with ducted combustion air kit

Viessmann · Vitocrossal 200 CI2 1500 and 2000

Clearance needed between boiler and drip pocket on large models.

  1. Install the drip pocket according to CAN/CSA B149.1 or NFPA 54.
  2. On CI2 1500 and 2000 with a ducted combustion air filter kit, leave at least 16 in. (400 mm) between the boiler and the drip pocket.

Electrical installation code

Viessmann · B2HA 112, 150, 399, 530

Electrical work must meet the current National Electrical Code in the USA or the Canadian Electrical Code in Canada, plus state, provincial and local rules.

  1. Confirm the code edition and local amendments before wiring.
  2. Wire field connections per the wiring diagram and component legend.

Electrical supply and wiring to the boiler control

Viessmann · Vitodens 100-W B1HE and B1KE

The boiler control is powered at 120 VAC, single phase, 60 Hz, rated 12 A. Install a disconnect and power service switch as local code requires. Outdoor sensor wiring must stay away from line voltage.

  1. Confirm supply is 120 VAC, 1 phase, 60 Hz, 12 A before connecting.
  2. Install a disconnect and service switch per local code.
  3. Route outdoor sensor cable away from 120 VAC or higher wiring.

Electrostatic discharge precaution

Viessmann · Vitodens 200-W B2HA 45, 60

Electronic modules can be damaged by electrostatic discharge.

  1. Before working on electronic modules, touch a grounded object such as a heating or water pipe to discharge static.

Emergency mode in a cascade

Viessmann · Viessmann cascade systems

Emergency mode starts when lag boilers lose communication with the lead boiler. The boilers then run at a user-set temperature until communication returns.

  1. Set the emergency mode temperature in the commissioning assistant or ViGuide app.
  2. Restore communication between lead and lag boilers to exit emergency mode.

Emissions test circuit jumpers

Viessmann · Vitotronic 300-K MW1S with emissions test switch S1

Both jumpers must be removed before the emissions test circuit is connected.

  1. Remove both jumpers before connecting the emissions test circuit.

Establish a WiFi connection

Viessmann · WiFi connection

WiFi must be switched on first. Hidden networks can be added by entering the network name (SSID) and password. An error message appears if the connection fails. The connection exists only if the WiFi itself is connected to the internet.

  1. Make sure WiFi is switched on.
  2. Open Settings, then 'Internet', then 'Network selection'.
  3. Select the WiFi network from the list. For a hidden network, enter the SSID and password.
  4. Confirm.
  5. If the network is protected, enter the password (maximum 40 characters) and confirm.
  6. Confirm the internet use prompt.

Expansion tank and boiler pump placement in a multi-circuit system

Viessmann · Vitodens 200-W B2HA 45, 60 with DHW tank and low-loss header

In the example layout with DHW storage, a low-loss header and mixing-valve circuits, the expansion tank has a specific location and the boiler-side pumps must pump into the boiler.

  1. Locate the expansion tank as shown in the system layout.
  2. Pipe pumps C and K so they pump into the boiler, as illustrated.
  3. Confirm the boiler pump and mixing-valve pump functions are set by coding address 53 where the pump output is used.

Expansion tank precharge

Viessmann · Expansion tank

If the precharged nitrogen pressure in the expansion tank is less than the static system pressure, the membrane must be inflated.

  1. Inflate the membrane to slightly above the system static pressure.
  2. Size the expansion tank correctly. An undersized tank lets fresh water enter through the fill valve and causes premature section failure, which is not covered by warranty.

Factory calibration and high altitude operation

Viessmann · Vitodens 100-W B1HE and B1KE

The burner is factory calibrated, so no field gas adjustment is expected. For high altitude sites up to 10,000 ft (3,000 m), set the electronic elevation in the boiler software; no input derate is needed.

  1. Confirm the gas type (natural gas or LPG) matches the boiler rating.
  2. At altitude above sea level, set the electronic elevation in the boiler software.
  3. Check that the gas supply pressure is within the min and max values in the specification table.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.