Commissioning: Boiler tips (part 6 of 21)
Short, practical technician tips on commissioning for boiler. Check each one against the manual for your exact model before acting.
Carbon monoxide alarm required
Viessmann · Vitorond 200 VD2A
The installer must confirm that at least one carbon monoxide alarm is installed in the living space or home, following the alarm maker's instructions and local codes, before the boiler is put into operation.
- Confirm a CO alarm is installed in the residential living space before start-up.
- Install the alarm per the manufacturer's instructions and local code.
Carbon monoxide detectors and maintenance
Viessmann · Vitotrol 200A with Viessmann boiler
Follow local rules for installing carbon monoxide detectors. Follow the Viessmann maintenance schedule for the boiler. The heating contractor must show the owner the equipment, safety requirements and shutdown procedure, and advise annual professional service before each heating season.
- Install carbon monoxide detectors per local regulations.
- Follow the boiler maintenance schedule.
- Review the shutdown procedure and the need for annual service with the owner before the heating season.
Cascade control amp load and isolation relays
Viessmann · Cascade control, Applications 9 and 10
The cascade control can carry a maximum of 6 amps. Isolation relays may be needed when the current draw of field-supplied components is exceeded.
- Add up the current draw of field-supplied circulators and mixing valve motors.
- If the total exceeds 6 amps, fit isolation relays.
Cascade heat generator scan and output entry
Viessmann · Versatronik 200 cascade, output boiler stage list
After a restart or new configuration, the controller scans the bus for about one minute. Output values cannot be entered during this scan. A generator that reports its output is entered automatically. A generator that reports no output is entered as 15 kW and can be changed by hand. Identical boilers only need one release each.
- Wait for the SCAN display to finish (about 1 minute).
- Select the boiler and stage with the Prog button.
- Enter or adjust the HS output value; use --- for not available and 0 for available but deactivated.
- Check the entered output matches the actual boiler.
Cascade setup for maximum burner count
Viessmann · Versatronik 200 multi-boiler cascade
To keep as many burners running as possible, set the next-boiler threshold to zero and the minimum modulation to the lowest stage value.
- Set Mod % next boiler on to 0.
- Set Modulation Min to the minimum modulation degree of the heat generator stages.
- Check that the boiler on-delay in the burner control matches the controller setting.
Cascade wiring layout for 4 boilers
Viessmann · Application 10, 4-boiler cascade
The Application 10 diagram shows boilers #1 to #4, each with power and a LON cable connection to the cascade control. Circulators P1.1 to P1.4 are shown with power connections.
- Connect power to each boiler and to circulators P1.1 to P1.4.
- Connect a LON cable from each boiler to the cascade control.
- Use the diagram in the manual for the full wiring layout. Only the labels are legible in the extracted text.
Central heating only without DHW heating
Viessmann · Vitotronic 300-K MW1B and Vitotronic 100 GC1B
There is no program for central heating without DHW. To get central heating only, the DHW heating is kept at a low setpoint. DHW is not heated unnecessarily, while DHW tank frost protection stays active.
- Select the heating program Heating and DHW.
- Set the DHW temperature to 50° F (10° C).
Change mixing valve rotation direction
Viessmann · Systems with mixing valve actuator
The rotation direction of the mixing valve is set with coding address CA (see page 49). Modular-Divicon systems need the rotation reversed. The source table of factory default direction per piping layout is not legible in this extract.
- Change the rotation direction with coding address CA (see page 49 of the manual).
- For systems with Modular-Divicon, reverse the rotation direction.
- If the mixing valve insert must be converted, follow the mixing valve installation instructions.
- Check the result with the relay test (outputs 7 and 9).
Check and set expansion tank precharge
Viessmann · Vitotron 100 VLN2 expansion tank
The expansion tank is precharged to 12 psi at the factory. Its Schrader valve is reached from the bottom of the boiler.
- Access the Schrader valve from the bottom of the boiler.
- Connect a pressure gauge to read the tank pressure.
- Use a pump to add air if the precharge is low.
- Match the precharge to the system pressure requirement if needed.
Check before enabling central heating
Viessmann · Vitotronic 300-K
Before relying on central heating, confirm the heating circuit, room temperature, heating program and time program are set. Heating circuit selection only applies when the system has more than one circuit.
- Select the heating circuit to change, if the system has several.
- Set the required standard room temperature.
- Set the heating program to the required option.
- Set the time program for central heating.
- Allow time for the rooms to reach the set temperature when planning time phases.
Check burner cycling before leaving site
Viessmann · Hydrostat 3250-Plus and other burner controls
Confirm the burner switches on and off correctly on a real call for heat before leaving the job. Failure to do this can cause a boiler runaway with risk of damage, injury or death.
- Call for heat at the thermostat and confirm the burner fires.
- Let the setpoint be reached and confirm the burner shuts off.
Check burner motor rotation at commissioning
Viessmann · 3 PH 208, 460 or 575 V burners on VD2/VD2A/CT3 controls
Three-phase burner motors can run backwards if the phases are wired wrong. Correct it at the burner terminals, not in the control.
- Check motor rotation against the arrow on the burner.
- If the rotation is wrong, disconnect power.
- Reverse wires BK1 and BK2 on the burner terminals.
Check burner motor rotation at commissioning (3-phase)
Viessmann · 3-phase burner motor supply (208, 460 or 575 V)
On 3-phase burners, the motor must turn in the direction marked on the burner. If it turns the wrong way, the wires must be swapped. Power must be off before any change.
- During commissioning, check the burner motor rotation.
- If the motor turns opposite to the direction marked on the burner, disconnect the power supply.
- Reverse wires BK1 and BK2 on the burner terminals.
- Restore power and recheck rotation.
Check coding addresses C7 and C9 for underfloor heating with heat exchanger
Viessmann · Vitotronic 200-H HK1B, underfloor heating with heat exchanger
In System Example 2 (underfloor heating circuit with heat exchanger), the coding addresses 00:2 to 00:10 are set automatically with a DHW tank. Also observe coding addresses C7 and C9 in the group "Heating circuit...".
- Check coding addresses C7 and C9 in the group "Heating circuit...".
Check combustion air leakage in the coaxial vent
Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199
Simple leak test on the coaxial air intake gap during start-up.
- Measure CO2 in the combustion air in the coaxial gap of the air intake pipe using the port on the vent adaptor.
- Pass if CO2 is no higher than 0.2% or O2 is no lower than 20.6%.
- If the readings fail, check the venting system thoroughly.
Check connections and perform combustion analysis
Viessmann · Commissioning checks
Check all primary and secondary connections for leaks. Take a CO measurement before and after work on gas appliances.
- Check heating system and domestic hot water connections for leaks.
- Correct leaks at fittings, pumps and valves.
- Take a CO measurement before and after work (see page 31).
- Record combustion values in the sequence given in the maintenance record on page 105.
Check heating circuit allocation label
Viessmann · Vitotronic 300-K, MW1S
Before changing any adjustments, confirm the heating circuit allocation label is attached to the matching field on the programming unit. Press the correct heating circuit button before making changes.
- Check that the heating circuit allocation label is on the correct field of the programming unit.
- Press the matching heating circuit button before adjusting anything.
Check heating circuit assignment stickers
Viessmann · Vitotronic 300 GW2
Confirm the heating circuit stickers are in place before any setting. Press the matching circuit button before each adjustment.
- Check that the assignment stickers are on the correct positions on the control unit.
- Press the matching heating circuit button before starting each setting.
Check heating circuit sticker assignment
Viessmann · Vitotronic 300 GW2
Confirm the heating circuit assignment stickers are on the correct spots on the control unit before settings are changed.
- Check that the assignment stickers for the heating circuits are placed in the right locations on the control unit.
- Press the matching circuit button before starting each setting.
Check heating water connections for leaks
Viessmann · Vitocrossal 300 CA3B Series 2.5 to 6.0
Check all heating water connections for leaks, including the connections for control equipment and the minimum pressure monitor (low-water indicator). Only open heating water connections when the boiler is unpressurized. Working on pressure-loaded parts is dangerous. Under-pressure can damage the boiler, so empty it only with open ventilation using a suction pump.
- Confirm the boiler is unpressurized before opening any heating water connection.
- If emptying the boiler, open the ventilation and use a suction pump. Do not create a vacuum in the boiler.
- Check the heating water connections and the low-water indicator connections for leakage.
- After about 500 hours of initial run, check all heating water side connections for leaks again.
Check LWCO function after installation
Viessmann · Low water cut-off device, Vitotronic 300
Test the low water cut-off function once the installation is finished.
- Complete the LWCO wiring and remove the jumper on the Power Pump Module board.
- Check that the LWCO device stops the burner when it should.
Check rating plate for CombiPLUS compatibility
Viessmann · Vitodens 100-W WB1B with CombiPLUS
Not every boiler works with the CombiPLUS kit. Confirm the rating plate states compatibility before fitting it.
- Read the boiler rating plate on WB1B-26 or WB1B-35.
- Confirm it lists CombiPLUS compatibility before installing the kit.
Check the boiler rating plate for CombiPLUS compatibility
Viessmann · WB1B-26, WB1B-35 with CombiPLUS kit
Before fitting the CombiPLUS kit, confirm the boiler rating plate on WB1B-26 or WB1B-35 states it is compatible with the kit.
- Read the boiler rating plate.
- Confirm it states CombiPLUS compatibility before installing the kit.
Check the design examples on site
Viessmann · Heating system designs
The application examples are recommendations only and must be checked on site for completeness and function. A low water cut-off must be installed where local codes require it. Proper installation and function in the field is the responsibility of the heating contractor.
- Field verify piping and all components against the chosen system version.
- Install a low water cut-off where local codes require it.
Check the heating circuit allocation label
Viessmann · Vitotronic 300-K MW1S programming unit
Confirm the heating circuit allocation label is in place before making any changes.
- Check that the heating circuit allocation label is affixed to the matching field of the programming unit.
- Press the matching button before making any adjustments.
Check the power supply protection before connecting
Viessmann · Power supply to Power Pump Module, Vitotronic 300
The Power Pump Module supply must have overcurrent protection rated at most 15 A, and the ground must be connected.
- Confirm the main supply to the Power Pump Module has overcurrent protection of 15 A or less.
- Make sure L, N and G are not swapped.
- Connect the ground. The equipment must be grounded.
Check three-phase burner motor rotation
Viessmann · Three-phase burners, VD2/VD2A/CT3
Caution: a motor running backwards is a known risk on three-phase burners. Check rotation at commissioning and correct it at the burner terminals, never on the control.
- Power up the burner and observe motor rotation.
- If rotation does not match the burner direction, disconnect all power first.
- Reverse the BK1 and BK2 wires on the burner terminals.
Chimney sizing and insulation
Viessmann · Vitorond 200 VD2 boilers
Relatively cool flue gases can cause corrosive condensation in an oversized or poorly insulated chimney.
- Design the chimney for the actual boiler model and its input; do not size it from the flue outlet.
- If a calculated diameter falls between two sizes, select the larger one.
- Insulate the chimney connection between the boiler vent collar and the chimney.
- Use a chimney that is gas tight when the Category III option is used.
Choose boiler control method by command state
Viessmann · Boiler 1-16 command state points AO301-316
Boilers can be driven by a modulation percentage (Boiler On) or by a temperature set point (Auto mode). Pick the command state for each boiler.
- Set command state to 1 to run the boiler on the command value percentage.
- Set command state to -1 (0xFF) to run the boiler on its set point.
- Set command state to 0 to turn the boiler off.
Clearance to combustible construction for hot water piping
Viessmann · All VR1 models
Keep 2 in of clearance around non-insulated hot water pipes to combustible construction. With adequate pipe insulation the clearance can be reduced to 0 in.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.