Short, practical technician tips on button combinations for boiler. Check each one against the manual for your exact model before acting.

Fault history access

Viessmann · Vitotronic 200-H

Opens the stored fault history. Details are on page 29.

  1. Press the rw and OK keys together for about 2 seconds to open.
  2. Press OK to exit.

Footer buttons on the service display

Viessmann · Vitocrossal 300 CA3B service display

The footer has icon buttons for home, back or cancel, help text, fault or service messages, and menu scrolling. The icons themselves are not visible in the extracted text, so check the manual image for the exact symbol.

  1. Use the home button to return to the home screen.
  2. Use the back button to go up one menu level or cancel a setting in progress.
  3. Use the help button for the help text.
  4. Use the message button to view fault or service messages.
  5. Use the scroll button to move through the menu.

Heat domestic hot water outside the programmed time

Viessmann · Vitotronic 300 GW2

Starts a one-off DHW heating cycle without changing the time program.

  1. Press the heating circuit selector button until it lights up.
  2. Press the DHW button (marked g in the manual) twice, 2 to 3 seconds apart.

Jump to system overview from a menu

Viessmann · Vitodens 100-W B1HE and B1KE control unit

Press and hold the Back button from inside any menu to jump straight to the system overview.

  1. From any menu, press and hold the Back button for about 4 seconds.

Load and end coding set 1

Viessmann · Vitotronic 200-H

Loads coding set 1 (coding page 50).

  1. Press the 9 and w keys together for about 2 seconds to load.
  2. Press the 9 and w keys together for about 1 second to end.

Load and end coding set 2

Viessmann · Vitotronic 200-H

Loads coding set 2 (coding page 53).

  1. Press the w and rw keys together for about 2 seconds to load, then confirm with OK.
  2. Press the 9 and rw keys together for about 1 second to end.

OK + menu hold to open service functions

Viessmann · Vitodens 200-W B2HA 112, 150, 399, 530

Holding OK and menu together for about 4 seconds opens the service functions menu, which includes the set-up wizard.

  1. Press OK and menu together for about 4 seconds.
  2. Select Service Functions.

One-off DHW heating outside the programmed times

Viessmann · Vitotronic 200-H DHW heating

Starts a single DHW heating cycle outside the set program.

  1. Press the DHW boost button (g) twice, 2 to 3 seconds apart.

One-time DHW boost outside the cycles

Viessmann · Vitotrol 300 remote control

Pressing the party key twice, about 2 to 3 seconds apart, gives one-time DHW production outside the programmed cycles.

  1. Press the party mode key once.
  2. Wait 2 to 3 seconds.
  3. Press the party mode key again to start one-time DHW production.

Open service functions or coding level 1

Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199

Press OK and the second button shown in the manual at the same time for about 4 seconds to open the service menu. Coding level 1 is also opened this way.

  1. Press OK and the second button shown in the manual together for about 4 seconds.
  2. Select 'Service functions' or 'Coding level 1' from the menu.

Open Service screen on Viessmann control

Viessmann · Vitotronic 300-K and related controls

Press OK and Menu together to bring up the Service screen. Hold for about 2 seconds, then use the arrow keys to reach Service Functions.

  1. Press OK and Menu together and hold for about 2 seconds.

Open the Service menu

Viessmann · Viessmann boiler controls behind the Versatronik gateway

Hold OK and Menu together to open the Service screen on the boiler control.

  1. Press OK and Menu together for about 2 seconds.

Open the short help guide

Viessmann · Vitotronic 300-K (type MW2B)

A short guide explains the controls and heating circuit selection.

  1. If the screen saver is active, press the help key.
  2. From anywhere in the menu, press the back key until the standard menu shows, then press the help key.

Panel buttons: power, scroll and adjust

Viessmann · Vitotron 100 VLN2 control panel

The panel uses three buttons: power (9), scroll (4) and up/down (5/6).

  1. Press the power button 9 to turn the panel on or to return to the main view.
  2. Press the scroll button 4 to move through the working parameters.
  3. Press the up or down buttons 5/6 to change the highlighted value.

Party key: extend heating time

Viessmann · Versatronik COMO OT Party key

The Party key sets how long heating is extended at comfort temperature. Pressing it briefly shows the current extension for about 3 seconds. Each press changes it by one hour. Holding it for 3 seconds keeps heating on until the next day.

  1. Press the Party key to show the current extension for about 3 seconds.
  2. Press the key again to add or remove one hour per press.
  3. Hold the key for 3 seconds to keep heating at comfort until the next day. The display briefly shows PARTY.
  4. To end the function, press the mode selector switch.

Party key: extend the heating time (comfort mode)

Viessmann · Versatronik COMO OT

Extends the comfort heating period by one hour per press. A 3-second press keeps the heating circuit at comfort until the next day. The display briefly shows PARTY. The Mode selector switch ends the function.

  1. Press the Party key to show the current extension for about 3 seconds.
  2. Press the Party key again to start setting, then press + or - to change it by one hour per press.
  3. Hold the Party key for 3 seconds to heat until the next day.
  4. To cancel, press the Mode selector switch.

Put the boiler into summer (stand-by) mode

Viessmann · Vitotron 100 VLN2, all models 04 to 14.4

Keep the power on between heating seasons. Hold the power button for about 3 seconds to switch to stand-by. The panel goes off, only the stand-by dot blinks, and the heating elements stay off while the pump runs on a daily timer.

  1. Leave the 120 VAC and 240 VAC supply on.
  2. Press and hold the power button (9) for 3 seconds.
  3. Confirm the panel is off and only the stand-by dot is blinking.

Remote reset of boiler error

Viessmann · Versatronik COMO OT

Some boilers allow a remote reset of their errors from this controller.

  1. During a fault, press ECO and PARTY together for several seconds.
  2. Check that the error message disappears.
  3. If the fault repeats, call the installation technician.

Return the boiler to winter (heating) mode

Viessmann · Vitotron 100 VLN2, all models 04 to 14.4

Bring the boiler back out of stand-by so the heating elements can run again.

  1. Press and hold the power button (9) for 3 seconds.
  2. Check that the panel lights up and the heating mode indicators show.

Service level button combinations overview

Viessmann · Vitotronic 100 GC1 service levels

Summary of how to open each service level and how to exit it.

  1. Temperatures, boiler coding cards and scans: press 9 and the rw buttons together for about 2 seconds; exit with OK (page 93).
  2. Relay test: press 9 and OK together for about 2 seconds; exit with OK (page 89).
  3. Participant check with LON: press w and OK together for about 2 seconds; press them together for about 1 second to start the check; exit by the same method (page 88).
  4. Operating status information: press the arrow button; exit with the arrow button (page 97).
  5. Service display: press OK to exit (page 98).

Set maximum heating input (service functions)

Viessmann · Vitodens 200-W B2HA 45, 60

The heating input can be limited through the modulation range. The upper limit is set by the boiler coding card. DHW input is limited separately through coding 6F in coding level 2.

  1. Press OK and the second button named in the manual together for about 4 seconds.
  2. Select Service functions.
  3. Select Maximum output.
  4. Select Change? and choose Yes.
  5. A value flashes (for example 85, which is 100% of rated input in factory setting). Select the required value.

Set the maximum heating output

Viessmann · Vitodens 222-F B2TB 19, 35, 68, 125

The heating output can be limited through the modulation range. The value shown is a percentage of rated output.

  1. Press OK and the second button together for about 4 seconds.
  2. Select Service functions, then Maximum output.
  3. Select Change? and then Yes.
  4. A value flashes on the display (for example 85, which is 100% of rated output in the factory setting). Select the required value.

Show acknowledged fault messages

Viessmann · Vitotronic 200-H

Recalls faults that were already acknowledged. Details are on page 37.

  1. Press and hold OK for about 2 seconds.
  2. Press OK to exit.

Start and end participant check (LON)

Viessmann · Vitotronic 200-H with LON system

Used with a LON system to check participants. Details are on page 15.

  1. Press the w and OK keys together for about 2 seconds to start.
  2. Press the w and OK keys together for about 1 second to end.

Start and end relay test

Viessmann · Vitotronic 200-H

Opens the relay test menu. Details are on page 16.

  1. Press the 9 and OK keys together for about 2 seconds to start.
  2. Press OK to end.

Start and end the participant check

Viessmann · Vitocontrol-S VD2/CT3/CM2 used as fault manager

Button sequence to start and end the LON participant check on the fault manager. The second button symbol is not legible in the extract.

  1. Press the w button and the second button (symbol not legible) at the same time for about 2 seconds to start the participant check.
  2. To end the participant check, press the w button and the second button together for about 1 second.

Start the filling program

Viessmann · Vitodens 200-W B2HA 80 to 100, 285 to 352

Runs the filling function from the service menu.

  1. Press OK and menu together for about 4 seconds.
  2. Select 'Service functions', then 'Filling'.
  3. Press OK or the back key to end the filling function.

Start the venting function from the service menu

Viessmann · Vitodens 222-F B2TB 19, 35, 68, 125

Enter the service functions menu with a button combination, then select the venting function.

  1. Press OK and the second button together for about 4 seconds.
  2. Select Service functions.
  3. Select Venting (bleeding). The venting function is enabled.
  4. To end venting, press OK or the back button.

Switch between winter and summer mode

Viessmann · Vitotron 100 VLN2 control panel

Holding the power button for 3 seconds changes the operating mode.

  1. Press and hold the power button 9 for 3 seconds to go into summer (stand-by) mode.
  2. Press and hold the power button 9 for 3 seconds to return to winter (heating) mode.

Switch off DHW heating

Viessmann · Vitocrossal 300 CA3B with Vitotronic 300 GW6C

Turns off DHW heating by setting the DHW temperature to the lowest value.

  1. From the home screen, open Menu, then DHW.
  2. Open DHW temperature.
  3. Select 50°F (10°C).
  4. Press OK to confirm.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.