Weil-McLain Boiler: Burner tries to light, then waits about an hour before the next try
Burner tries to light, then waits about an hour before the next try on a Weil-McLain boiler: Each call gets up to 5 light-off tries. After a failed try the gas valve closes, the blower runs a postpurge and the control starts over. After the 5th failure in a row it waits 60 minutes, then tries again on its own.
Applies to: ECO Tec 80, 110, 150, 199 Series 3 (heat only)
Common causes of burner tries to light, then waits about an hour before the next try
- Electrode did not see a flame signal at the end of the ignition period, 5 times in a row
How to fix burner tries to light, then waits about an hour before the next try: step by step
- Safety first: turn off power at the service switch before touching wiring. Gas-side work is for a qualified gas technician only.
- Read the fault name on the home screen before you reset anything.
- Hold the WM logo for 7 seconds to open the contractor menu, then go to Diagnostics to see current and past lockouts.
- In Boiler Settings, check Boiler Model, Fuel Type (natural gas or propane) and Altitude against the rating plate and the job site. The manual calls these critical settings.
- On a 199 or 199C, check that the blower type picked in the control (EF90 or NG150) matches the label on the blower.
- Watch one light-off: prepurge at ignition speed, then spark and gas valve open together, spark stops and the control checks flame through the electrode.
- Flame and lockout fault details are in the ECO Tec Boiler Manual troubleshooting section, not in this manual.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain ECO Tec Series 3 Advanced Manual 550-100-600/1025, sec. Control action / Sequence of operation, p.3; Contractor menus p.57; Boiler Settings p.58. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.