Updated · by Aurora Star Tech Inc.

Wire combustion air blower through adaptor on a Viessmann boiler: Blower is powered through the combustion air device adaptor and needs a proving switch.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: VD2/VD2A/CT3 and CM2 boilers

How to fix wire combustion air blower through adaptor: step by step

  1. Disconnect power to control and burners.
  2. Install combustion air device adaptor (Part No. 7134 563) on the DIN rail in the connection enclosure, or in the boiler junction box on CM2.
  3. Connect the blower to the adaptor: 120 VAC, max 5 FLA, use AWG 14 wire.
  4. Connect the proving switch (normally open, rated 120 VAC) as shown in the diagram.
  5. Provide disconnect means and overcurrent protection as required by local codes.
  6. Confirm the blower is suitable for this application.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 45-46. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.