Viessmann Boiler: Wire a combustion air damper on a common interface
Wire a combustion air damper on a common interface on a Viessmann boiler: Wire the combustion air damper motor, proving switch and power through the Common Combustion Air Device Interface.
Applies to: Combustion air damper, common interface
How to fix wire a combustion air damper on a common interface: step by step
- Disconnect power to the control and the burner.
- Connect the damper motor (120 VAC, 5 FLA max) to the common interface.
- Wire the proving switch rated for 120 VAC.
- Connect the 120 VAC power supply.
- Size the fuse from the damper manual's current rating.
- Provide a disconnect and overcurrent protection as local codes require.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitocontrol-S VD2/CT3/CM2
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
Vitotronic 100 GC1
Source: Vitotronic 100 GC1 / Vitocontrol-S installation manual, p. 59. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.