Viessmann Boiler: Wire a combustion air damper
Wire a combustion air damper on a Viessmann boiler: Wire the combustion air damper to the boiler control through the combustion air device adaptor in the connection enclosure. Use the damper manual for the correct install. Confirm the damper is rated for this application.
Applies to: Combustion air damper wiring, single boiler
How to fix wire a combustion air damper: step by step
- Disconnect power to the control and the burner.
- Wire the damper per the diagram: adaptor in the connection enclosure, field-supplied 120 VAC relay coil, damper, end switch rated 120 VAC, and 120 VAC supply.
- Wire the end switch to the normally open terminal on the device adaptor board.
- Provide a disconnect and overcurrent protection as local codes require.
- Spring return dampers do not need the field-supplied relay.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitocontrol-S VD2/CT3/CM2
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
Vitotronic 100 GC1
Source: Vitotronic 100 GC1 / Vitocontrol-S installation manual, p. 56. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.