Viessmann Boiler: Water side connections and flow protection
Water side connections and flow protection on a Viessmann boiler: The boiler is only for forced circulation hot water systems. Connect supply and return headers and safety piping while keeping air venting and check valve requirements in mind.
Applies to: Vitorond 200 VD2 320 to 1080
How to fix water side connections and flow protection: step by step
- Thoroughly flush the heating system, especially when retrofitting to an existing system.
- Install the supply and return headers and make all heating system connections.
- Install a spring-loaded flow check valve just downstream of the circulation pump in the heating supply. This helps stop water flowing into space heating circuits during DHW priority or summer operation.
- Do not install an isolation valve between the boiler and the safety header.
- Route the discharge pipe so it cannot scald people.
- Remove air with air vents and avoid piping that can trap air.
- Meet all requirements in the System Design Guidelines and Technical Data Manual.
- Install the safety piping.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 200, VD2 Series 320 to 1080 Installation Instructions, p. 20. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.