Viessmann Boiler: Venting safety requirements and draft checks
Venting safety requirements and draft checks on a Viessmann boiler: The vent must carry all combustion products safely outdoors and must never pass through return, supply, ventilating or combustion air ducts. The boiler must never run without a vent. Check the building for exhaust devices that could depressurize it, and tell the owner in writing if they could affect the appliance.
Applies to: Vitorond 100 VR1 oil-fired boilers
Common causes of venting safety requirements and draft checks
- Blocked vent, chimney or termination from birds' nests, ice, snow or debris
- Unlined chimney or improper size
- Downdraft or condensation in the flue
- Positive-pressure mechanical draft connected to the vent
How to fix venting safety requirements and draft checks: step by step
- Confirm the vent is not blocked and terminates outdoors.
- Check the chimney is lined, sized and in good condition.
- Confirm the chimney gives enough draft in the mildest weather the boiler will run in.
- Connect the boiler only to a chimney used for no other appliance, unless code allows it.
- Correct any downdraft or condensation problem before finishing.
- Check oil appliances have sufficient draft at all times.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 100 VR1 installation and service instructions, p. 17. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.