Viessmann Boiler: Venting – Category I (chimney) and Category III (positive pressure)
Venting - Category I (chimney) and Category III (positive pressure) on a Viessmann boiler: The boiler is approved as a Category I appliance when vented to a chimney, and as a Category III positive pressure non-condensing boiler when using the positive pressure option. Side wall venting is not approved. The chimney must be designed for the low flue gas temperatures, and its size is not set by the vent collar diameter.
Applies to: Vitorond 200 VD2A boilers
Common causes of venting - category i (chimney) and category iii (positive pressure)
- Chimney lacks sufficient insulation or is oversized, causing corrosive condensation
- Flue gases cool too quickly in the chimney
How to fix venting - category i (chimney) and category iii (positive pressure): step by step
- Do not use side wall venting.
- Design the chimney for the cool flue gases at partial load.
- Insulate the chimney connection between the boiler vent collar and chimney.
- If the calculated chimney diameter falls between two sizes, select the larger size.
- Install a barometric draft regulator in the chimney/vent (Category I).
- Vent each boiler individually.
- Use AL29-4C stainless steel single-wall vertical venting (UL/ULC listed for Category III) for positive pressure venting.
- Make sure the chimney is gas tight for Category III venting.
- Follow local codes; in the USA use the National Fuel Gas Code ANSI Z223.1 for gas or NFPA 31 for oil; in Canada use CAN/CSA B149.1 or .2 for gas or CSA B-139 for oil.
- Do not stand on the top panel when installing or insulating overhead piping or venting.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 200 VD2A Technical Data Manual, p. 23-24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.