Viessmann Boiler: Two-stage burner dew-point protection
Two-stage burner dew-point protection on a Viessmann boiler: The burner should go to full (second-stage) input when boiler water falls below the minimum to protect against condensation and corrosion. The burner must not be held in first-stage operation during summer.
Applies to: Two-stage burners
Common causes of two-stage burner dew-point protection
- Boiler water below 140 °F (60 °C) causes condensation.
How to fix two-stage burner dew-point protection: step by step
- Set the burner so it is not limited to first-stage operation in summer.
- Confirm the burner switches to second stage when boiler water falls below 140 °F (60 °C).
- Set the first-stage minimum inputs to the table values when used with a Vitotronic control.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 200 VD2A service instructions, p. 14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.