Updated · by Aurora Star Tech Inc.

System layout 6: DHW and three zone circuits on a Viessmann boiler: Example for one or more CU3A boilers with a DHW storage tank and three zone circuits. Zone 1 uses boiler output 157. Zones 2 and 3 use the AM1 extension module outputs A1 and A2. Zone circuit thermostats are dry contacts. DHW pump is on output 21 and DHW recirculation pump on output 28/20. A low-loss header may be used if required.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitocrossal 300 CU3A with DHW tank and three zone circuits

How to fix system layout 6: dhw and three zone circuits: step by step

  1. Wire zone thermostats 1, 2 and 3 as dry contacts.
  2. Connect zone 1 to output 157.
  3. Connect zone 2 to output A1 and zone 3 to output A2 on the AM1 extension module.
  4. Connect DHW pump to output 21 and DHW recirculation pump to output 28/20.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199

Source: Vitocrossal 300 CU3A Installation Instructions, p. 49. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.