Viessmann Boiler: Start-up with antifreeze in the system (flow reading error)
Start-up with antifreeze in the system (flow reading error) on a Viessmann boiler: At low ambient start-up with antifreeze, the flow reading can fail. A special start-up procedure warms the fluid so flow can be read.
Applies to: Vitotron 100 VLN2 with antifreeze
Common causes of start-up with antifreeze in the system (flow reading error)
- Low ambient temperature at start-up
- Physical properties of the antifreeze solution
How to fix start-up with antifreeze in the system (flow reading error): step by step
- If the flow indicator flickers and the cut-off valves are open, close the OP and TT contacts.
- This starts the special start-up procedure automatically.
- Wait while the panel alternates parameters with dash marks (-, --, ---).
- The procedure ends and normal operation starts once minimum flow is reached.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
VLN2 04VLN2 06VLN2 08VLN2 12VLN2 14.4
Source: Vitotron 100 VLN2 installation and service instructions, p. 15. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.