Viessmann Boiler: Sizing the electric boiler
Sizing the electric boiler on a Viessmann boiler: Size the boiler from a heat loss analysis. Do not oversize, since this adds cost to the boiler, wiring and materials.
Applies to: Vitotron 100 VLN2
How to fix sizing the electric boiler: step by step
- Run a heat loss analysis for the heated space.
- Convert the BTU/h load to kW by dividing by 3,413. Example: 33,513 BTU / 3,413 = 9.81 kW.
- Choose a boiler that slightly exceeds the kW requirement, by no more than 20%.
- For larger loads, cascade boilers in a parallel configuration as described in the piping section.
- If using propylene glycol, do not exceed a 50/50 glycol to water ratio. Glycol reduces heat transfer and efficiency.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
VLN2 04VLN2 06VLN2 08VLN2 12VLN2 14.4
Source: Vitotron 100 installation and service instructions, p. 7. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.