Viessmann Boiler: Single-boiler vs multi-boiler coding with external controls
Single-boiler vs multi-boiler coding with external controls on a Viessmann boiler: Set coding 01 for the system type. Multi-boiler systems need plugs aVD and aVH wired.
Applies to: Single and multi-boiler systems
How to fix single-boiler vs multi-boiler coding with external controls: step by step
- Single-boiler system: set coding 01: 1 (factory setting). With a building automation system, only plug aVD is required.
- Set boiler water temperature to the minimum value.
- Multi-boiler system: set coding 01: 3.
- Wire both plugs aVD and aVH. DHW tank and load-dependent cascade control must run through the building automation system.
- The boiler activation contact is essential. The lead boiler contact must stay constantly closed.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitotronic 100, GC1 installation manual, p. 61. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.