Viessmann Boiler: Single combustion air device on multiple boiler systems
Single combustion air device on multiple boiler systems on a Viessmann boiler: Common combustion air interface for several boilers.
Applies to: Multi-boiler systems with common combustion air interface
How to fix single combustion air device on multiple boiler systems: step by step
- Install a combustion air device adaptor (part 7134 563) on each boiler.
- Install the common combustion air device interface (part 7134 604) as per its manual.
- Wire the interconnecting cable between the adaptors and the common interface (field supplied).
- Wire the common interface to the blower (120 VAC, max 5 FLA), proving switch (120 VAC) and power supply as shown.
- Disconnect power to the control and burner before wiring. Provide disconnect and overcurrent protection as required by local codes.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Viessmann Vitotronic 100 GC1 installation manual, pp. 69-70. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.