Updated · by Aurora Star Tech Inc.

Simplified flue system leak check on a Viessmann boiler: Checks the balanced flue annular gap for leaks by measuring combustion air.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 222-F B2TB 19, 35, 68, 125

How to fix simplified flue system leak check: step by step

  1. Measure the CO2 concentration of the combustion air in the coaxial gap of the air intake pipe using measuring port A on the vent adaptor.
  2. Accept the vent as sufficiently leak-proof if CO2 is no higher than 0.2% or O2 is no lower than 20.6%.
  3. If CO2 is higher or O2 is lower, check the venting system thoroughly.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

222-F B2TB 19222-F B2TB 35222-F B2TB 68222-F B2TB 125B2TB 19B2TB 35B2TB 68B2TB 125VD2T 1HC1T4ZP.01VD2T 1HC1T4ZV.01Vitodens 222-F, B2TB 19Vitodens 222-F, B2TB 35Vitodens 222-F, B2TB 68Vitodens 222-F, B2TB 125

Source: Vitodens 222-F B2TB service instructions, p. 22. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977