Viessmann Boiler: Shut down the boiler and open the combustion chamber door for service
Shut down the boiler and open the combustion chamber door for service on a Viessmann boiler: Isolate the boiler and open the chamber before any cleaning or inspection.
Applies to: VR1 40 to 63, 161 to 245
How to fix shut down the boiler and open the combustion chamber door for service: step by step
- Make sure main power to the boiler, the heating system and all external controls is off, and take steps so nobody can switch it back on.
- Close the main oil supply valve near the burner and the one near the tank.
- Disconnect power to the boiler.
- Remove the front panel by lifting it up and out.
- Remove the two bolts on the combustion chamber door and open the door.
- Remove the flue gas turbulators if fitted.
- Remove the combustion chamber insert if fitted.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 100 installation and service manual, p. 48. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.