Viessmann Boiler: Set expansion tank and system pressures
Set expansion tank and system pressures on a Viessmann boiler: Follow the expansion tank maker's instructions. Max operating pressure is 75 psig (5 bar), or 58 psig (3.9 bar) in some Canadian provinces.
Applies to: All VD2 sizes 320 to 1080
Common causes of set expansion tank and system pressures
- Low inlet pressure in the expansion tank
How to fix set expansion tank and system pressures: step by step
- Drain the system or close the cap valve on the expansion tank and bleed the tank pressure to 0 psig.
- If the tank inlet pressure is below the static system pressure, add nitrogen until the inlet is 1.5 to 3 psig (0.1 to 0.2 bar) above static.
- Fill with water until the cold fill pressure is 1.5 to 3 psig (0.1 to 0.2 bar) above the tank inlet pressure.
- Do not exceed 75 psig (5 bar), or 58 psig (3.9 bar) where required.
- Check that the sight glass gasket and hose are airtight.
- Test water hardness and treat the water if the mineral content is high.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitorond 200 VD2 Series 320 to 1080 Service Instructions, p. 12. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.