Viessmann Boiler: Set CO2 at upper heating output
Set CO2 at upper heating output on a Viessmann boiler: Adjust CO2 at full load. Only the burner being adjusted may run; the other burners must be at standstill.
Applies to: CA3B 2.5 to 6.0
How to fix set co2 at upper heating output: step by step
- Open the gas shut-off valve.
- Start the burner with the emissions test switch enabled at the control unit.
- Press the button until the service display shows 100 (100%).
- Read the CO2 level at the flue pipe.
- If CO2 is out of range, remove cap B.
- Turn adjusting screw A in small steps with a 3 mm Allen key. Clockwise lowers CO2 (less gas). Counter-clockwise raises CO2 (more gas).
- Record the value in the maintenance report on page 162.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CA3B 2.5 BoilerCA3B 3.0 BoilerCA3B 3.5 BoilerCA3B 4.0 BoilerCA3B 5.0 BoilerCA3B 6.0 BoilerCA3B Series 2.5CA3B Series 3.0CA3B Series 3.5CA3B Series 4.0CA3B Series 5.0CA3B Series 6.0Vitocrossal 300 CA3B 2.5Vitocrossal 300 CA3B 3.5Vitocrossal 300 CA3B 4.0Vitocrossal 300 CA3B 5.0Vitocrossal 300 CA3B 6.0Vitocrossal 300 CA3B Series 2.5Vitocrossal 300 CA3B Series 3.0Vitocrossal 300 CA3B Series 3.5Vitocrossal 300 CA3B Series 4.0Vitocrossal 300 CA3B Series 5.0Vitocrossal 300 CA3B Series 6.0
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 67. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.