Viessmann Boiler: Set CO2 at lower heating output
Set CO2 at lower heating output on a Viessmann boiler: Adjust CO2 at partial load after setting full load.
Applies to: CA3B 2.5 to 6.0
How to fix set co2 at lower heating output: step by step
- Press the button until the service indicator drops to 0 (lower heating output).
- Measure CO2 at the flue gas pipe.
- If CO2 must change, unscrew cover cap B.
- Turn adjusting screw A in small steps with a Torx 40. Clockwise raises CO2. Counter-clockwise lowers CO2.
- Record the reading in the maintenance record on page 162.
- Start the upper and lower outputs again from the control unit and recheck both values.
- Press the two buttons shown as S E and D together for more than 2 seconds to return the burner to operating mode.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CA3B 2.5 BoilerCA3B 3.0 BoilerCA3B 3.5 BoilerCA3B 4.0 BoilerCA3B 5.0 BoilerCA3B 6.0 BoilerCA3B Series 2.5CA3B Series 3.0CA3B Series 3.5CA3B Series 4.0CA3B Series 5.0CA3B Series 6.0Vitocrossal 300 CA3B 2.5Vitocrossal 300 CA3B 3.5Vitocrossal 300 CA3B 4.0Vitocrossal 300 CA3B 5.0Vitocrossal 300 CA3B 6.0Vitocrossal 300 CA3B Series 2.5Vitocrossal 300 CA3B Series 3.0Vitocrossal 300 CA3B Series 3.5Vitocrossal 300 CA3B Series 4.0Vitocrossal 300 CA3B Series 5.0Vitocrossal 300 CA3B Series 6.0
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 68. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.