Viessmann Boiler: Service (maintenance) display
Service (maintenance) display on a Viessmann boiler: The Service message and symbol appear once the hours-run or time limits set in coding 21 and 23 in the Boiler group are reached. The limit values are not listed on these pages. If service is done early, coding 24:1 stays set and must be changed to 24:0, or Service will show again the following Monday.
Applies to: Vitotronic 300 GW6B boiler control unit
Common causes of service (maintenance) display
- Hours-run or time limit from coding 21 or 23 has been reached
How to fix service (maintenance) display: step by step
- Tap Confirm when the Service message appears.
- If several faults are showing, tap Service messages to view the list.
- Carry out the maintenance.
- If service was done early, set coding 24:1 in the Boiler group to 24:0.
- Or from the home screen: Menu, Service, enter viservice, Service functions, Reset service.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300 GW6B installation and service instructions, p. 61. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.