Viessmann Boiler: Sensor wiring near high voltage
Sensor wiring near high voltage on a Viessmann boiler: Long sensor runs can pick up electromagnetic interference. Keep sensor wiring away from 120/240 VAC conductors. If that is not possible, use stranded, twisted pair or shielded wire and ground only one end of the shield.
Applies to: All Vitotronic 300 GW2 sensor and extension wiring
How to fix sensor wiring near high voltage: step by step
- Route sensor wire away from 120/240 VAC conductors.
- If a crossing cannot be avoided, use stranded, twisted pair or shielded wire.
- Ground only one end of the shield.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300 Installation and Service Instructions, p. 25. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.