Updated · by Aurora Star Tech Inc.

Return valve protection with low-loss header (Circuit Diagram 8) on a Viessmann boiler: When return temperature falls below the minimum, the return valve on the boilers closes proportionally via sensor T1 to protect the boiler.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Circuit Diagram 8, multi-boiler system with low-loss header

Common causes of return valve protection with low-loss header (circuit diagram 8)

  • Return temperature below required minimum

How to fix return valve protection with low-loss header (circuit diagram 8): step by step

  1. Verify sensor T1 is connected at plug aJA and coding 4A is set to 4A: 1.
  2. Verify continuous return temperature control is set (0C: 1).
  3. Size each boiler circuit pump so its supply is at least equal to the maximum possible total heating circuit supply; recommendation is 110%.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Viessmann Vitotronic 100 GC1 installation and service instructions, p. 22. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.