Viessmann Boiler: Return temperature protection with shunt pump (Circuit Diagram 5)
Return temperature protection with shunt pump (Circuit Diagram 5) on a Viessmann boiler: Sensor T2 switches on the shunt pump when return temperature falls below the minimum. If the minimum is still not reached, reduce supply at least 50% using sensor T1 through the isolation valve or the heating circuit controls.
Applies to: Multi-boiler system with manifold close to boiler
Common causes of return temperature protection with shunt pump (circuit diagram 5)
- Return temperature below required minimum
How to fix return temperature protection with shunt pump (circuit diagram 5): step by step
- Confirm sensor T2 switches the shunt pump on when return temperature is low.
- If minimum return temperature is not reached, set supply reduction of at least 50% via sensor T1.
- Size the shunt pump so bypassed water is about 30% of the total boiler supply rate.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitotronic 100 GC1 installation and service instructions, p. 16. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.