Viessmann Boiler: Reset manual reset temperature limit switches
Reset manual reset temperature limit switches on a Viessmann boiler: The supply water and flue gas temperature limit switches lock out mechanically when the probe temperature goes over the limit. The switches are factory preset and must not be adjusted.
Applies to: CA3B Series 2.5 to 6.0
Common causes of reset manual reset temperature limit switches
- Probe temperature exceeded the limit setpoint
How to fix reset manual reset temperature limit switches: step by step
- Confirm the probe has cooled by about 14 F (8 C) below the limit temperature.
- Unscrew the reset cap and set it aside.
- Press to reset the switch.
- Reinstall the reset cap.
- If the switch will not reset, replace the switch.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CA3B 2.5 BoilerCA3B 3.0 BoilerCA3B 3.5 BoilerCA3B 4.0 BoilerCA3B 5.0 BoilerCA3B 6.0 BoilerCA3B Series 2.5CA3B Series 3.0CA3B Series 3.5CA3B Series 4.0CA3B Series 5.0CA3B Series 6.0Vitocrossal 300 CA3B 2.5Vitocrossal 300 CA3B 3.5Vitocrossal 300 CA3B 4.0Vitocrossal 300 CA3B 5.0Vitocrossal 300 CA3B 6.0Vitocrossal 300 CA3B Series 2.5Vitocrossal 300 CA3B Series 3.0Vitocrossal 300 CA3B Series 3.5Vitocrossal 300 CA3B Series 4.0Vitocrossal 300 CA3B Series 5.0Vitocrossal 300 CA3B Series 6.0
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 service instructions, p. 59. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.