Viessmann Boiler: Replacing the coding card or display and programming unit
Replacing the coding card or display and programming unit on a Viessmann boiler: Coding card and display replacement on the burner control unit.
Applies to: Vitocrossal 300 CA3B 2.5 to 6.0
How to fix replacing the coding card or display and programming unit: step by step
- Disconnect KM-BUS connector.
- Undo the 2 mounting screws and tighten to 9 lb.in (1 Nm) on reinstall.
- Lift the display and programming unit and disconnect its connecting cable plug.
- Remove the display and programming unit.
- To change the coding card, pull it from the burner control unit and insert the new card.
- To change the display, install the new unit in reverse order.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CA3B 2.5 BoilerCA3B 3.0 BoilerCA3B 3.5 BoilerCA3B 4.0 BoilerCA3B 5.0 BoilerCA3B 6.0 BoilerCA3B Series 2.5CA3B Series 3.0CA3B Series 3.5CA3B Series 4.0CA3B Series 5.0CA3B Series 6.0Vitocrossal 300 CA3B 2.5Vitocrossal 300 CA3B 3.5Vitocrossal 300 CA3B 4.0Vitocrossal 300 CA3B 5.0Vitocrossal 300 CA3B 6.0Vitocrossal 300 CA3B Series 2.5Vitocrossal 300 CA3B Series 3.0Vitocrossal 300 CA3B Series 3.5Vitocrossal 300 CA3B Series 4.0Vitocrossal 300 CA3B Series 5.0Vitocrossal 300 CA3B Series 6.0
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 54. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.