Updated · by Aurora Star Tech Inc.

Replace rotary damper and servomotor on a Viessmann boiler: For CA3B 3.5 to 6.0, the rotary damper must be fully open when the burner is off and while it runs. An incompletely open damper can cause malfunction or show incorrect servomotor adjustment.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: CA3B Series 2.5 to 6.0, rotary damper for 3.5 to 6.0

Common causes of replace rotary damper and servomotor

  • Incomplete damper opening
  • Incorrect servomotor adjustment

How to fix replace rotary damper and servomotor: step by step

  1. Disconnect the servomotor connector.
  2. Undo the 4 screws on the damper retaining bracket (torque 13 lb.in / 1.5 Nm) and remove the damper with the bracket.
  3. Undo the 2 screws on the servomotor axis (torque 3 lb.ft / 4 Nm) and remove the servomotor.
  4. Release the articulated rod on the damper with an open-ended wrench.
  5. Install the new damper, air pressure switch and servomotor in reverse order.
  6. If needed, adjust the damper with the articulated rod so it is fully open. Use the servomotor settings in the service instructions.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

CA3B 2.5 BoilerCA3B 3.0 BoilerCA3B 3.5 BoilerCA3B 4.0 BoilerCA3B 5.0 BoilerCA3B 6.0 BoilerCA3B Series 2.5CA3B Series 3.0CA3B Series 3.5CA3B Series 4.0CA3B Series 5.0CA3B Series 6.0Vitocrossal 300 CA3B 2.5Vitocrossal 300 CA3B 3.5Vitocrossal 300 CA3B 4.0Vitocrossal 300 CA3B 5.0Vitocrossal 300 CA3B 6.0Vitocrossal 300 CA3B Series 2.5Vitocrossal 300 CA3B Series 3.0Vitocrossal 300 CA3B Series 3.5Vitocrossal 300 CA3B Series 4.0Vitocrossal 300 CA3B Series 5.0Vitocrossal 300 CA3B Series 6.0

Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 service instructions, p. 64. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.