Viessmann Boiler: Remove burner and check burner gasket
Remove burner and check burner gasket on a Viessmann boiler: Burner removal for inspection and cleaning. Hook the burner into its service retainer, not on its dome matrix.
Applies to: Vitocrossal 300 CU3A burner service
How to fix remove burner and check burner gasket: step by step
- Switch off the main power and the ON/OFF switch at the control unit.
- Close the gas shut-off valve and secure against reopening.
- Unplug fan motor H, gas valve C, ionization electrode D and plug G.
- Disconnect the gas supply pipe E fitting and pull the air intake adaptor A.
- Remove the four nuts B and remove burner F, then hook it into service retainer L.
- Check burner gasket K for damage and replace if needed. Replace every 2 years.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
CU3I 2ZC2ZP.01CU3I 3HC/Z3ZP.01CU3X 1ZC1ZP.01Vitocrossal 300 CU3A 26Vitocrossal 300 CU3A 35Vitocrossal 300 CU3A 45Vitocrossal 300 CU3A 57Vitocrossal 300 CU3A 94Vitocrossal 300 CU3A 125Vitocrossal 300 CU3A 160Vitocrossal 300 CU3A 199
Source: Viessmann Vitocrossal 300 CU3A 26 to 199 Service Instructions, p. 22. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.