Viessmann Boiler: Reading and changing the boiler sequence
Reading and changing the boiler sequence on a Viessmann boiler: The digits in the basic display show the boiler numbers in the current actual sequence. Hyphens show status: boilers before the first hyphen are activated, boilers between the hyphens are available but not needed, and boilers after the second hyphen are blocked (for example by a fault). The operator-requested sequence can differ from the actual sequence, because faults and the heating contractor's settings can change it. The sequence criteria are set by the heating contractor at start-up, and sometimes no alternative sequence is available.
Applies to: Multi-boiler systems with Vitocontrol-S, VD2/CT3/CM2
How to fix reading and changing the boiler sequence: step by step
- Open the hinged cover on the programming unit.
- Press the button combination to show the alternative operator-requested sequence (shown without hyphens); hold for about 2 seconds.
- Press the button(s) until the required boiler sequence appears.
- Press the confirm button; the display returns to the actual boiler sequence.
- Close the hinged cover.
If the unit shows an error code, look it up: Viessmann Boiler codes
More settings shortcuts tips for boiler
Source: Vitocontrol-S VD2/CT3/CM2 operating instructions, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.