Viessmann Boiler: Quick heat-up, quick setback and economy functions
Quick heat-up, quick setback and economy functions on a Viessmann boiler: Quick heat-up and quick setback change the room set point by at least 2 K (3.6 °F) until the set room temperature is reached. Economy functions switch the heating circuit pump off and drop the supply set point to 0 °C (32 °F).
Applies to: Heating circuits with room temperature input
How to fix quick heat-up, quick setback and economy functions: step by step
- Quick heat-up: press the party button or change from reduced to normal heating mode.
- Quick setback: press the economy button or change from normal to reduced heating mode.
- Economy pump logic: set outdoor cut-off with coding A5.
- Extended economy: check outdoor cut-off A6, room set reduction A9, mixing valve economy A7 (12 minutes closed) and room limit b5.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
300-K MW1Vitocontrol-S, VD2/CT3/CM2, 300-K MW1
More settings shortcuts tips for boiler
Source: Vitocontrol-S VD2/CT3/CM2 installation and service instructions, p. 131. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.