Viessmann Boiler: Pump selection and low-loss header logic
Pump selection and low-loss header logic on a Viessmann boiler: Pump selection must be based on accurate system flow and pressure drop calculations, including DHW sizing. The boiler has a factory-set integrated boiler/system pump, and its flow must be selected based on Ut. With a low-loss header connected, the boiler's built-in LLH logic manages Ut through sensor communication with the header.
Applies to: Vitodens 222-F, B2TB 68 and 125
How to fix pump selection and low-loss header logic: step by step
- Calculate system flow and pressure drop, including DHW sizing.
- Confirm system flow is within boiler max and min flow limits.
- Install a low-loss header if flow exceeds max, falls below min, or is unknown.
- Connect the Viessmann low-loss temperature sensor for single-boiler use.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
222-F B2TB 19222-F B2TB 35222-F B2TB 68222-F B2TB 125B2TB 19B2TB 35B2TB 68B2TB 125VD2T 1HC1T4ZP.01VD2T 1HC1T4ZV.01Vitodens 222-F, B2TB 19Vitodens 222-F, B2TB 35Vitodens 222-F, B2TB 68Vitodens 222-F, B2TB 125
More commissioning tips for boiler
Source: Vitodens 222-F B2TB application guide, p. 14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.