Viessmann Boiler: Provisional burner operation with external dry contact (BMS)
Provisional burner operation with external dry contact (BMS) on a Viessmann boiler: Use this to hand heat demand and modulation to an external controller.
Applies to: Vitotronic 300 GW6B with burner interface
How to fix provisional burner operation with external dry contact (bms): step by step
- Remove the jumper across terminals 23 (L) and 24 (L).
- Connect terminals 23 (L) and 25 (L) to an external dry contact (heat demand on close).
- On demand the boiler holds low fire until the BMS controls modulation.
- Wire the BMS modulation contacts to T6, T7 and T8 at plug 90 as described in the manual.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300, GW6B installation and service instructions, p. 39. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.