Updated · by Aurora Star Tech Inc.

Pressure relief valve installation on a Viessmann boiler: Install the factory-supplied approved pressure relief valve on the boiler water supply connection. Do not put an isolation valve between the boiler and the relief valve. Pipe the discharge close to a floor drain, never outdoors.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitorond 100 VR1 40 to 63, 161 to 245

How to fix pressure relief valve installation: step by step

  1. Install the pressure relief valve on the boiler water supply connection.
  2. Install the discharge pipe, minimum 3/4 in, unthreaded at the end.
  3. End the discharge pipe about 6 in (150 mm) above a floor drain.
  4. Orient the discharge pipe so it cannot scald people.
  5. Do not install any isolation valve between the boiler and the relief valve.
  6. Check that the expansion tank piping is at least 3/4 in.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Source: Vitorond 100 VR1 installation and service instructions, p. 20. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.