Viessmann Boiler: Piping the boiler in a heating/cooling system with a chiller
Piping the boiler in a heating/cooling system with a chiller on a Viessmann boiler: When the boiler shares a system with a chiller, the chilled water must be piped in parallel with the boiler and isolated by valves so chilled water cannot enter the boiler. Coils in the air handlers can expose the boiler loop to refrigerated air, so flow control or another automatic method is needed to stop gravity circulation during cooling. Follow the chiller maker's requirements as well.
Applies to: Vitocrossal 300 CA3B Dual Fuel with chiller or cooling coils
How to fix piping the boiler in a heating/cooling system with a chiller: step by step
- Pipe the chilled water in parallel with the boiler.
- Install valves so chilled water cannot enter the boiler.
- Fit flow control valves or another automatic means to stop gravity circulation of boiler water during cooling.
- Set valve V2 open and V1 closed for cooling season, and V1 open and V2 closed for heating season.
- Attach metal tags to the changeover valves.
- Run the system circulating pump from its own on/off switch, not from the boiler control.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
2.53.04.05.06.0CA3B 2.5CA3B 3.0CA3B 3.5CA3B 4.0CA3B 5.0CA3B 6.0CA3B Dual Fuel 2.5CA3B Dual Fuel 2.5 BoilerCA3B Dual Fuel 3.0CA3B Dual Fuel 3.0 BoilerCA3B Dual Fuel 3.5CA3B Dual Fuel 3.5 BoilerCA3B Dual Fuel 4.0CA3B Dual Fuel 4.0 BoilerCA3B Dual Fuel 5.0CA3B Dual Fuel 5.0 BoilerCA3B Dual Fuel 6.0CA3B Dual Fuel 6.0 BoilerCA3B Dual Fuel Series 2.5CA3B Dual Fuel Series 3.0CA3B Dual Fuel Series 3.5CA3B Dual Fuel Series 4.0CA3B Dual Fuel Series 5.0CA3B Dual Fuel Series 6.0Vitocrossal 300 CA3B Dual Fuel 2.5Vitocrossal 300 CA3B Dual Fuel 3.0Vitocrossal 300 CA3B Dual Fuel 3.5Vitocrossal 300 CA3B Dual Fuel 4.0Vitocrossal 300 CA3B Dual Fuel 5.0Vitocrossal 300 CA3B Dual Fuel 6.0Vitocrossal 300 CA3B Dual Fuel Series 2.5Vitocrossal 300 CA3B Dual Fuel Series 3.0Vitocrossal 300 CA3B Dual Fuel Series 3.5Vitocrossal 300 CA3B Dual Fuel Series 4.0Vitocrossal 300 CA3B Dual Fuel Series 5.0Vitocrossal 300 CA3B Dual Fuel Series 6.0
Source: Vitocrossal 300 CA3B Dual Fuel installation manual, p. 48. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.