Viessmann Boiler: Piping the boiler for heating/cooling (chilled water) use
Piping the boiler for heating/cooling (chilled water) use on a Viessmann boiler: When the boiler works with a chiller, the chilled medium must be piped in parallel with the boiler using valves that keep chilled water out of the boiler. Flow control valves or other automatic means must stop gravity circulation of boiler water during cooling. The circulating pump must run from a separate on/off switch, not from the boiler control. Metal tags should identify the seasonal valves.
Applies to: Vitocrossal 300 CA3B Dual Fuel in heating/cooling applications
Common causes of piping the boiler for heating/cooling (chilled water) use
- Gravity circulation of boiler water during the cooling cycle.
How to fix piping the boiler for heating/cooling (chilled water) use: step by step
- Pipe the chilled medium in parallel with the boiler.
- Fit valves V1 and V2 and tag them with metal tags.
- Fit flow control valves or other automatic means to stop gravity circulation.
- Power the circulating pump from a separate on/off switch, not from the boiler control.
- Check the chiller manufacturer's requirements.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
2.53.04.05.06.0CA3B 2.5CA3B 3.0CA3B 3.5CA3B 4.0CA3B 5.0CA3B 6.0CA3B Dual Fuel 2.5CA3B Dual Fuel 2.5 BoilerCA3B Dual Fuel 3.0CA3B Dual Fuel 3.0 BoilerCA3B Dual Fuel 3.5CA3B Dual Fuel 3.5 BoilerCA3B Dual Fuel 4.0CA3B Dual Fuel 4.0 BoilerCA3B Dual Fuel 5.0CA3B Dual Fuel 5.0 BoilerCA3B Dual Fuel 6.0CA3B Dual Fuel 6.0 BoilerCA3B Dual Fuel Series 2.5CA3B Dual Fuel Series 3.0CA3B Dual Fuel Series 3.5CA3B Dual Fuel Series 4.0CA3B Dual Fuel Series 5.0CA3B Dual Fuel Series 6.0Vitocrossal 300 CA3B Dual Fuel 2.5Vitocrossal 300 CA3B Dual Fuel 3.0Vitocrossal 300 CA3B Dual Fuel 3.5Vitocrossal 300 CA3B Dual Fuel 4.0Vitocrossal 300 CA3B Dual Fuel 5.0Vitocrossal 300 CA3B Dual Fuel 6.0Vitocrossal 300 CA3B Dual Fuel Series 2.5Vitocrossal 300 CA3B Dual Fuel Series 3.0Vitocrossal 300 CA3B Dual Fuel Series 3.5Vitocrossal 300 CA3B Dual Fuel Series 4.0Vitocrossal 300 CA3B Dual Fuel Series 5.0Vitocrossal 300 CA3B Dual Fuel Series 6.0
Source: Viessmann Vitocrossal 300 CA3B Dual Fuel installation manual, p. 48. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.