Viessmann Boiler: Mounting the front part of the control unit (VD2/VD2A/CT3)
Mounting the front part of the control unit (VD2/VD2A/CT3) on a Viessmann boiler: Refit the front housing after wiring. Keep the flat cable and programming unit cable routed through the cable guides in the cover.
Applies to: Vitotronic 300 GW2 with VD2, VD2A or CT3 control
How to fix mounting the front part of the control unit (vd2/vd2a/ct3): step by step
- Position the front housing and clip its hinges onto the counter-parts on the main housing.
- Release the stay bar, open the front up and lock the stay bar at point A.
- Insert the flat cable from the Optolink into plug X20.
- Insert the programming unit plug into socket X10 and route the cable through the cover guides.
- Engage the stay bar in the front housing.
- Close the front housing.
- Secure the front housing with the supplied screws.
- Install the connection enclosure cover and secure it with the supplied screw.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitotronic 300 GW2 installation and service instructions, p. 57-58. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.