Viessmann Boiler: Mixing valve reduction for return temperature (Circuit Diagram 6)
Mixing valve reduction for return temperature (Circuit Diagram 6) on a Viessmann boiler: When return temperature falls below the minimum, the mixing valves are partly or fully closed via sensor T1.
Applies to: Circuit Diagram 6, common supply pump and low-pressure manifold
Common causes of mixing valve reduction for return temperature (circuit diagram 6)
- Return temperature below required minimum
How to fix mixing valve reduction for return temperature (circuit diagram 6): step by step
- Verify sensor T1 is connected at plug aJA (4A: 1).
- Set coding 0d: 1 so Therm-Control applies to downstream mixing valves.
- Size the common supply pump on 110% of the total supply output of the heating system.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Viessmann Vitotronic 100 GC1 installation and service instructions, p. 18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.