Viessmann Boiler: Mixing valve motor direction check
Mixing valve motor direction check on a Viessmann boiler: During the actuator test, the supply temperature must rise when the mixing valve opens. If it drops, the motor is turning the wrong way or the mixing valve set is fitted incorrectly.
Applies to: Mixing valve circuits HC2 and HC3
Common causes of mixing valve motor direction check
- Motor turning in the wrong direction
- Mixing valve set fitted incorrectly
How to fix mixing valve motor direction check: step by step
- Run the actuator test and open the mixing valve.
- Watch the supply temperature.
- If it falls, check the motor direction and the mixing valve fitting against the mixing valve installation instructions.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitotronic 300, GW6B installation and service instructions, p. 53. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.